- 52 -
Failure code
Failure name
Occurrence condition
Control when occurring
Removal condition
CHxx090
Individual Inletwater temperature sensor error
Individual Inletwater temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx091
Individual Outletwater temperature sensor error
Individual Outletwater temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx093
Control box inner temperature sensor error
Control box inner temperature sensor is short/open
Stop applicable cycle
Automatically return to normal condition
CHxx104
Communication Error between Outdoor Unit
Communication Error between Outdoor Unit
Stop applicable cycle
Automatically return to normal condition
CHxx105
Fan board communication error
Fan board communication error
Stop applicable cycle
Automatically return to normal condition
CHxx106
Fan PCB IPM fault
Fan PCB IPM fault
Stop applicable cycle
Automatically return to normal condition
CHxx107
Fan DC link low voltage error
Fan DC link low voltage
Stop applicable cycle
Automatically return to normal condition
The phenomena from main component failure