Troubleshooting Guide
94
Universal System Air Conditioner
Check the IPM (Measuring after Comp connector disconnect)
1) Test mode set diode mode( )
RD(+)
RD(+)
BK(-)
BK(-)
P
N W
V
U
P
N W
V
U
Measuring method
A
B
Terminal
P
N
W
V
U
U
V
W
0.4~0.6V
0.4~0.6V
0.4~0.6V
0.4~0.6V
0.4~0.6V
0.4~0.6V
Measuring method A
Measuring method B
Troubleshooting CH21