126 Universal System Air Conditioner
Outdoor Units
Outdoor Units
1.Basic control
1.1 Normal operation
❈
PID : Proportional Integrate Derivative
1.2 Compressor control
Frequency Control:Frequency that corresponds to a room capacity will be determined according to the room
temperature, outdoor temperature and the difference in the temperature of a room and the temperature set by
the remote controller.
Cooling mode
Heating mode
Stop state
Compressor
Step Control
Step Control
stop
Fan
Step Control
Step Control
After 30sec, Off
EEV
PID Control
PID Control
After 60sec, Full Open
4 way valve
Off
On
After 30sec, Off
Step_base
Standard frequency step by
∑
Qj (Summation of capacity code)
Long piping
Comp. Step compensation by setting long piping
∆
Step_TAO
step compensation by TAO (Outdoor temp.)
∆
Step_TAI
step compensation by TAI (Indoor temp.)
∆
Step_DTAI
Step Compensation of temperature difference Indoor Temp. and Setting Temp.
Comp_Step = (StLong piping compensation) x
∆
Step_TAO x
∆
Step_TAI x
∆
Step_DTAI
Summary of Contents for ABNH366GLAC
Page 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Page 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Page 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Page 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Page 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Page 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Page 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Page 154: ...P No MFL30301501 Printed in Korea ...