Service Manual 119
Ceiling Cassette Type
■
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
■
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 21°C.
The operation diagram is as following.
21
°
C
23
°
C
32
°
C
29
°
C
17
°
C
Pipe
temperature
OFF
Indoor fan
speed
LO
LOW
LOW
SELECTED
FAN
LOW
LOLOW
COMP
ON
COMP
Outdoor fan
Indoor fan
4way valve
Setting Temperature
+2
°
C(Unit Sensing)
0
°
C(Remo Sensing)
(Thermo ON)
Setting Temperature
+4
°
C(Unit Sensing)
+2
°
C(Remo Sensing)
(Thermo OFF)
Indoor unit
Heat-Exchanger
temperature
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
ON
ON
ON
ON
Low
Low
Low
Low
Low
Lo
Off
Off
Off
ON
OFF
OFF
Low fan during 10sec
A
B
Intake Air Temperature
35
°
C
32
°
C
29
°
C
21
°
C
17
°
C
Summary of Contents for ABNH366GLAC
Page 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Page 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Page 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Page 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Page 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Page 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Page 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Page 154: ...P No MFL30301501 Printed in Korea ...