Table 7-1
Static Pressure(mmAq)
Setting Value
0
2
4
6
8
10
12
14
15
Model Name
Step
CMM(CFM)
High
32(1130)
230
230
225
220
150
1
ABNH366GLAC
Med
29(1024)
240
238
237
235
230
220
Low
26.5(936)
245
245
243
243
240
240
High
36(1271)
238
235
230
225
220
215
ABNH426RLAC
Med
32(1130)
253
250
245
240
235
230
Low
28(989)
255
255
255
255
250
248
High
40(1412)
230
225
220
215
205
200
190
180
160
ABNH486RLAC
Med
35(1235)
250
245
240
235
230
220
215
210
200
Low
30(1059)
255
255
255
250
245
240
235
230
225
High
50(1766)
185
180
174
162
154
140
90
5
1
ABNH606RLAC
Med
45(1589)
210
205
199
191
189
180
155
138
110
Low
40(1423)
230
225
219
215
210
205
193
180
171
Note: 1. To get the desired Airflow & E.S.P combination from the table set the matching value from
the table. Value other than that in table will not give the combinations of airflow & ESP
which are mentioned in the table.
2. Table 7-1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Summary of Contents for ABNH366GLAC
Page 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Page 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Page 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Page 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Page 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Page 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Page 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Page 154: ...P No MFL30301501 Printed in Korea ...