Troubleshooting Guide
80
Universal System Air Conditioner
1. Self-diagnosis Function
■
Error Indicator
• The function is to self-diagnosis air conditioner and express the troubles identification if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble for error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Indoor Error
Error code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
00
No Error
ON
01
Indoor Room themistor error
1time
OFF
02
Indoor in-piping sensor error
2times
OFF
03
Remote controller error
3times
OFF
04
Drain Pump error
4times
OFF
05
Communcation error between in and out
5times
OFF
06
Indoor Out-Piping sensor error
6times
OFF
07
Differnt mode operation
7times
OFF
Outdoor Error
Error Code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
21
DC Peak (IPM Fault)
2times
1times
Off
22
CT 2(Max CT)
2times
2times
Off
23
DC Link Low Volt.
2times
3times
Off
24
L/H press SW
2times
4times
Off
25
Low voltage / Over voltage
2times
5times
Off
26
DC Comp Position Error
2times
6times
Off
32
D-Pipe High (INV)
3times
2times
Off
33
D-Pipe High (Normal)
3times
3times
Off
40
CT Sensor (Open / Short)
4times
O
Off
41
INV. D-PipeTh Error (Open / Short)
4times
1times
Off
44
Outdoor Air Th Error (Open / Short)
4times
4times
Off
45
Cond. Pipe Error (Open / Short)
4times
5times
Off
46
Suction Pipe Error (Open / Short)
4times
6times
Off
47
Const D-PipeTh Error (Open / Short)
4times
7times
Off
51
Over Capacity
5times
1times
Off
52
Comm. Error(Main micon <-> Sub micom)
5times
2times
Off
53
Comm. Error(Indoor <-> Outdoor)
5times
3times
Off
54
Outdoor 3 phase power supply
5times
4times
Off
Reverse phase / phase omission
60
EEPROM Check Sum Error
6times
O
Off
61
Cond. Pipe High
6times
1times
Off
62
Heatsink High
6times
2times
Off
63
Cond. Pipe Low
6times
3times
Off
65
Heatsink Th Error (Open/Short)
6times
5times
Off
67
Outdoor BLDC Fan Lock
6times
7times
Off
105
Comm. Error(Main board <->Fan board)
10times
5times
Off
Summary of Contents for ABNH366GLAC
Page 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Page 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Page 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Page 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Page 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Page 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Page 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Page 154: ...P No MFL30301501 Printed in Korea ...