Troubleshooting Guide
Service Manual
83
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)
Caused by the remote controller.
Caused by other parts except
the remote controller
When the mark (
) is displayed in LCD
screen, replace battery.
Check the contact of CN-DISP 1 connector
When the detect switch (double key) inside the
remote controller door is fault, it is impossible to
operate temperature regulating(
▲
/
▼
) and wind
speed selecting.
Check DISP PWB Ass'y
-Voltage between CN1
➀
-
➆
: DC +5V
Check the Display PWB Ass'y
• Check receiver ass'y
Product doesn't operate with the remote controller.
Trouble 2
Summary of Contents for ABNH366GLAC
Page 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Page 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Page 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Page 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Page 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Page 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Page 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Page 154: ...P No MFL30301501 Printed in Korea ...