Troubleshooting Guide
82
Universal System Air Conditioner
3. Electronic Parts Troubleshooting Guide
❇
Refer to electronic contorol device drawing & schematic diagram.
The Product doesn’t operate at all.
Turn off the main power and wait until LED on outdoor PCB is off.
Turn on the main power again.
Does "Beeping" sound is made from the indoor unit?
• Primarily, the operating condi-
tion of Micom is O.K.
• Check CN-DISP1
Check the voltage of power(AC220V/AC240V, 50Hz).
• The voltage of main power.
• The voltage applied to the unit.
• The connecting method of Indoor/Outdoor connecting cable (each color)
• The P.W.B. Ass'y
(Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.)
Trouble 1
NO
YES
The operation check of the P.C.B. Ass'y
Procedure
1) The input voltage of power trans-
former.
2) The output voltage of power
transformer.
3) IC01D(7812)
4) IC02D(7805)
5) IC01A(KIA7036)
Specification
1) AC230V ± 30V
: Check the rated voltage
2) 14V ± 3V
3) DC12V
4) DC5V
5) The voltage of micom pin 29
: DC4.5V
↑
Remedy
1) Replace
power transfomer.
2) Replace
power transfomer.
3) Replace IC01D.
4) Replace IC02D.
5) Replace IC01A.
Summary of Contents for ABNH366GLAC
Page 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Page 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Page 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Page 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Page 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Page 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Page 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Page 154: ...P No MFL30301501 Printed in Korea ...