Troubleshooting Guide
96
Universal System Air Conditioner
7) Troubleshooting CH23
23
DC Link Low voltage
• DC Link volt is below
300V
• Check point & Normal condition
• Check the TAB1 is connect.
• At not operating : DC Link voltage(260V
)
• At Comp operating : DC Link voltage(500V
)
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
1. Check the Tab1 connection condition. (Refer to outdoor wiring diagram)
2. Check the CN_COIL(IN), CN_COIL(OUT) connection condition.
3. Check the DC Link voltage at not operating(260V
)
4. Check the DC Link voltage at Comp operating(500V
)