Troubleshooting Guide
Service Manual
103
14) Troubleshooting CH54
54
3-phase wrong wiring
of main outdoor unit
• 3-phase wrong wiring of
outdoor unit (Reverse
Phase /omission of
phase)
• Abnormal Main PCB
• No connection of CN_Phase
• Changed R, S, T connection order
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
1. Check the connection condition of R,S,T wire.
2. Check the connection condition of CN_Phase.
3. Check the outdoor main fuse.
Summary of Contents for ABNH366GLAC
Page 64: ...64 Universal System Air Conditioner II Outdoor Units Introduction 65 AUUW C R410A 67 ...
Page 72: ...72 Universal System Air Conditioner Inverter SINGLE A AUUW368C AUUW368C1 3 Wiring Diagrams ...
Page 73: ...Service Manual 73 Inverter SINGLE A AUUW42 48 608C ...
Page 108: ...Electronic Control Device 108 Universal System Air Conditioner BG BR Series Ceiling Duct Type ...
Page 110: ...Electronic Control Device 110 Universal System Air Conditioner Outdoor Unit 1 Component side ...
Page 111: ...Electronic Control Device Service Manual 111 2 Solder side ...
Page 113: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 114: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 115: ...Schematic Diagram Service Manual 115 Ceiling Suspended ...
Page 154: ...P No MFL30301501 Printed in Korea ...