PROFINET interface – basic configuration
Leuze electronic
BPS 348i
53
8.6.1 Overview of the PROFINET modules
NOTICE
Overwriting of data by PLC!
Note that the PLC overwrites the data set via the service interface.
In the PROFINET configuration phase, all PROFINET parameters that were changed via the service
interface are overwritten. This also applies for the parameters from modules that were not configured.
During the configuration phase, the BPS receives parameter telegrams from the Controller (master).
Before the parameter telegrams are evaluated and the respective parameter values are set, all PRO
-
FINET parameters are reset to default values. This ensures that the parameters of modules that are
not selected are set to the default values.
NOTICE
Do not activate any universal modules!
If the control makes a so-called “universal module” available, the universal module may not be activat
-
ed for the BPS.
You can find the default values of the BPS in the module descriptions.
Module
Module name
Module contents
(P) = Parameter, (O) = Output, (I) = Input
DAP_001
see page 54
Maximum position value
Profile (P), Integration depth (P), Tape selection (P)
M1
see page 55
Maximum position value
Sign (P), Unit (P), Position resolution (P), Counting direction (P), Offset (P), Position (I)
M2
see page 56
Static Preset
Preset value (P), Teach Preset (O), Reset Preset (O)
M3
see page 56
Dynamic Preset
Preset value (P), Teach Preset (O), Reset Preset (O)
M4
see page 57
Input/output I/O 1
Function (P), Activation (P), Output (P), Input (P), State (I), Control output (O)
M5
see page 59
Input/output I/O 2
Function (P), Activation (P), Output (P), Input (P), State (I), Control output (O)
M6
see page 61
Status and control
Measurement value invalid/not active (I), Preset active (I), Teach Preset toggle (I),
Lower/upper position limit value 1 … 2 (I), Control/marker bar code detected (I), Control/
marker bar code toggle (I), Temperature warning/error (I) Hardware defect (I), Read
quality warning/Error threshold (I), Standby active (I), Start/stop measurement (O), Acti
-
vate/deactivate Standby (O), Acknowledge control/marker bar code (O)
M7
see page 62
Position limit value range 1
Upper/Lower pos. limit 1 (P)
M8
see page 63
Position limit value range 2
Upper/Lower pos. limit 2 (P)
M9
see page 63
Error handling procedures
Position value in the case of error (P), Suppress position state (P), Error delay/error
delay time (position) (P), Velocity in the case of error (P), Suppress velocity state (P),
Error delay/error delay time (velocity) (P)
M10
see page 64
Velocity
Velocity resolution (P), Averaging (P), Velocity (I)
M11
see page 65
Static velocity limit value 1
Switching type (P), Selection of direction (P), Velocity limit value 1 (P), Velocity
hysteresis 1 (P), Limit value 1 range start/range end (P)
M12
see page 66
Static velocity limit value 2
Switching type (P), Selection of direction (P), Velocity limit value 2 (P), Velocity
hysteresis 2 (P), Limit value 2 range start/range end (P)
M13
see page 67
Static velocity limit value 3
Switching type (P), Selection of direction (P), Velocity limit value 3 (P), Velocity
hysteresis 3 (P), Limit value 3 range start/range end (P)