8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00581
C00581
C00598
C00600
C00601
Parameter | Name:
C00581 | Resp. LS_SetError_x
Data type: UNSIGNED_8
Index: 23994
d
= 5DBA
h
SB
LS_SetError_1
: Selection of the error responses for application error messages
• An application error message is tripped by a FALSE-TRUE edge at the binary inputs
bSetError1...2
.
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00581/1
1: Fault
Resp. LS_SetError_1 bSetError1
C00581/2
1: Fault
Resp. LS_SetError_1 bSetError2
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00598 | Resp. to open circuit AINx
Data type: UNSIGNED_8
Index: 23977
d
= 5DA9
h
Configuration of monitoring of the analog input
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00598/1
1: Fault
Response to open circuit at AIN1 when being configured
as 4 ... 20 mA current loop
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00600 | Resp. to DC bus overvoltage
Data type: UNSIGNED_8
Index: 23975
d
= 5DA7
h
Configuration of monitoring of the motor control (group 3)
Selection list
1 Fault
2 Trouble
Subcodes
Lenze setting
Info
C00600/1
2: Trouble
Resp. to undervoltage in the DC bus
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00601 | Del. resp.to fault: DC bus overvoltage
Data type: UNSIGNED_16
Index: 23974
d
= 5DA6
h
Delay times for error responses
Setting range
(min. value | unit | max. value)
0.00
s
65.00
Subcodes
Lenze setting
Info
C00601/1
2.00 s
Delay time for error activation "DC-bus overvoltage"
• In case of DC-bus overvoltage, an error is only trans-
mitted after this delay time has elapsed.
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000