8400 BaseLine D | Software Manual
Error management
Error messages of the operating system
134
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
123
Motor
management /
encoder
8060945
OC2: Power section - earth fault
The device has detected an earth fault of the
motor phases. In order to protect the device
electronics, the inverter control is switched off.
Mostly, faulty motor connections are the reason.
If the sinusoidal filters, motor cable lengths and
cable types (capacity of shielding) are
misdimensioned, discharge currents to PE may
lead to this error message.
1: Error -
pulse inhibit
("Fault")
Check of the motor connections and
the corresponding plug connector at
the device.
Use of sinusoidal filters, cable lengths
and cable types recommended by
Lenze.
123
Motor
management /
encoder
8061033
OC6: I2xt motor overload
Thermal overload of the motor
Check whether the motor overload
threshold I²xt in code
is
dimensioned correctly.
Compliance with load requirements
and, if required, correction of
dimensioning. With control mode
VFCplus:
Check of the Vmin boost, see
For details see
125
Analog I/O
integrated
8192001
An01: AIN1 I < 4 mA
Check wiring of the analog input
terminal for open circuit.
Check minimum current values of the
signal sources.
144
Parameter set
9437185
PS01: No memory module
Memory module is not plugged in.
Either the memory module is not available or not
correctly engaged in the slot.
5: Warning
Plug in the memory module or make
sure that it is engaged correctly.
144
Parameter set
9437186
PS02: Invalid parameter set
Parameter set filing invalid due to a previously
incomplete saving of the parameter set (e.g. by
voltage failure or pulling out the memory
module during the saving process).
1: Error -
pulse inhibit
("Fault")
Please make sure during the saving
process that the voltage supply is kept
up and the module remains plugged
into the slot.
144
Parameter set
9437187
PS03: Parameter set of device invalid
Incompatibility of the parameter set is e.g.
caused if the parameter set in the memory
module has a higher version than the basic
device expects.
1: Error -
pulse inhibit
("Fault")
When exchanging the memory
modules, observe the downward
compatibility.
144
Parameter set
9437188
PS04: Invalid parameter set
A memory module incompatible for this device
has been detected.
1: Error -
pulse inhibit
("Fault")
If devices are exchanged, the
parameter sets of the memory module
for the device can be accepted by
= "1".
144
Parameter set
9437215
PS31: Parameter set of different power class
A parameter set of a memory module has been
detected with a different power class and motor
control SLVC (
= 4).
1: Error -
pulse inhibit
("Fault")
Execute the motor parameter
identification (
= "1").
400
Device hardware
defective
26214505
dH69: Adjustment data error
Adjustment data error - power section
1: Error -
pulse inhibit
("Fault")
The device must be returned to Lenze.
980
US01: User error 1 64225281
US01: User error 1
User error 1 of LS_SetError_1
Defined by the user
981
US02: User error 2 64290817
US02: User error 2
User error 1 of LS_SetError_1
Defined by the user
Subject area
Error no.
Error cause
Error
response
Remedy by the user
No.
Name