Firmware 03.00 - DMS EN 5.0 - 07/2009
L
175
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00003
C00003
C00002/17
0: Off / ready
Activate quick stop
"1"
≡
Activate quick stop
"0"
≡
Deactivate quick stop
C00002/18
0: Off / ready
Reserved
C00002/19
0: Off / ready
Reset error
• After the reset of the current error, other errors may
be pending which must be reset as well.
• Details on the currently pending error are displayed in
C00002/20
0: Off / ready
Reserved
C00002/21
0: Off / ready
Delete logbook
• All entries in the logbook of the controller will be de-
leted.
• Information about the error history is saved in the
logbook.
C00002/22
0: Off / ready
Reserved
C00002/23
0: Off / ready
Identify motor parameters
• This device command serves to carry out an automat-
ic identification of the motor parameters.
• The device command is only carried out if the control-
ler is in the Switched On status
• In order to identify the motor parameters, the con-
troller must be enabled after this device command.
C00002/24
0: Off / ready
Reserved
C00002/25
0: Off / ready
Reserved
C00002/26
0: Off / ready
Reserved
C00002/27
0: Off / ready
Reserved
C00002/28
0: Off / ready
Reserved
C00002/29
0: Off / ready
Reserved
C00002/30
0: Off / ready
Reserved
C00002/31
0: Off / ready
Reserved
C00002/32
0: Off / ready
Reserved
;
Read access
;
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00002 | Controller commands
Data type: UNSIGNED_8
Index: 24573
d
= 5FFD
h
Parameter | Name:
C00003 | Status of last device command
Data type: UNSIGNED_8
Index: 24572
d
= 5FFC
h
Status of the device command executed last (
).
Note:
Before switching off the supply voltage after executing a device command, check the successful execution of the
device command by means of this status display!
:
Selection list
(read only)
Info
0 Successful
Device command has been executed successfully.
1 Command unknown
Device command is implausible or not known in the sys-
tem.
2 No access
Access for required device command is not approved.
3 Time-out
Processing of the device command could not be executed
within the defined time (time-out).
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1