Motor control (MCTRL)
DC-injection braking
100
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
5.6
DC-injection braking
DC-injection braking allows the drive to be quickly braked to a standstill without the need
to use an external brake resistor.
The braking current can be defined with code
.
The maximum braking torque to be generated by the DC braking current is approx.
20 ... 30 % of the rated motor torque. It is lower than that for braking in generator mode
with an external brake resistor.
Automatic DC-injection braking (Auto-DCB) improves the starting performance of the
motor during operation without speed feedback.
Overview of the relevant parameters
DC-injection braking can be carried out in two ways with different types of activation:
Manual DC-injection braking (DCB)
Automatic DC-injection braking (Auto-DCB)
Parameter
INFO
Auto-DCB: threshold
Response threshold for activating the DC-injection braking
DCB: Current
Enter the current in [%]
Auto-DCB: hold time
DCB: hold time
See explanations for function block LA_NCtrl