3.
Connect the fan cable to the system board (see “System-board internal connectors” on page 118 for the
location of the rear fan connector).
4.
Install any adapters that you removed (see “Installing an adapter” on page 153).
5.
Go to “Completing the FRU replacement” on page 190.
Replacing the hard disk drive fan assembly
Use the following procedures to replace the hard disk drive fan assembly. These procedures apply only to
server models that have a hard disk drive fan assembly.
Attention:
v
Replace a failed fan within 48 hours.
v
To ensure proper cooling and airflow, do not operate the server for more than 30 minutes with the side
cover removed.
Removing the hard disk drive fan assembly
To remove the hard disk drive fan assembly, complete the following steps:
1.
Read the safety information that begins on page 1.
2.
Turn off the server and all attached devices; then, disconnect all power cords and external cables.
3.
Unlock and remove the side cover (see “Removing the side cover” on page 130).
4.
Rotate the rear adapter-retention bracket to the open (unlocked) position.
5.
Disconnect the hard disk drive fan assembly cable from the system board, making a note of the cable
was connected to the hard disk drive fan connector for later installation.
6.
Remove the lower bezel (see “Removing the two-piece bezel” on page 131).
7.
Remove the hard disk drives.
8.
Lift up and hold the drive cage release tab; then, rotate the drive cage out of the chassis until the
retaining tab on top of the cage locks into place.
Chapter 6. Replacing FRUs
165