Table 5. DSA Preboot messages (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
v
See Chapter 7, “Parts listing, TS200 Types 6522, 6523, 6524, 6525, 6526, 6528, 6529, and 6530,” on page 201 to determine which
components are customer replaceable units (CRU) and which components are field replaceable units (FRU).
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a Trained service
technician.
v
Go to the Lenovo support Web site at http://www.lenovo.com/support to check for technical information, hints, tips, and new
device drivers or to submit a request for information.
Message
number
Component
Test
State
Description
Action
405-901-xxx
Intel Ethernet
Device
Test MII Registers Failed
1.
Make sure that the component
firmware is at the latest level. The
installed firmware level is shown in
the DSA event log in the
Firmware/VPD section for this
component. For more information, see
“Updating the firmware” on page
258.
2.
Run the test again.
3.
Replace the component that is
causing the error. If the error is
caused by an adapter, replace the
adapter. Check the PCI Information
and Network Settings information in
the DSA event log to determine the
physical location of the failing
component.
4.
If the failure remains, go to the
Lenovo Web site for more
troubleshooting information at
http://www.lenovo.com/support.
405-902-xxx
Intel Ethernet
Device
Test EEPROM
Failed
1.
Make sure that the component
firmware is at the latest level. The
installed firmware level is shown in
the DSA event log in the
Firmware/VPD section for this
component. For more information, see
“Updating the firmware” on page
258.
2.
Run the test again.
3.
Replace the component that is
causing the error. If the error is
caused by an adapter, replace the
adapter. Check the PCI Information
and Network Settings information in
the DSA event log to determine the
physical location of the failing
component.
4.
If the failure remains, go to the
Lenovo Web site for more
troubleshooting information at
http://www.lenovo.com/support.
Chapter 4. Diagnostics
101
Summary of Contents for ThinkServer TS200 6522
Page 2: ......
Page 199: ...Chapter 6 Replacing FRUs 191 ...
Page 289: ......
Page 290: ...Printed in USA ...