53
Step 8: in
step
04, the quantity of IDUs needs to be confirmed manually. Main board of
each module will display:
Cycle
code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
04_Confirm the
quantity of IDUs
db
Light
04
Light
Quantity of
connected
IDUs
blink
If the quantity displayed is the same with actual quantity, then press SW7
confirmation button on the master unit to confirm it. Unit will start next
step
:
Cycle
code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
04_Confirm the
quantity of IDUs
db
Light
04
Light
OC
Light
Step 9:
step
05 is “
Check
ODU
internal communication”
If no error is detected, system will display as below and then start next
step
.
——
Cycle
code
Progress code Status code
Meaning
progress
LED1
LED2
LED3
Code Display
status code
Display
status Code
Display
status
05_
Check
ODU
internal
communication
db
Light
05
Light
OC
Light Detection is finished.
Start next
step
.
If error is detected, system will stay at current progress. Error has to be solved manually.
Below are relevant errors:
——
Cycle
code
Progress code Status code
Meaning
progress
LED1
LED2
LED3
Code Display
status code
Display
status Code
Display
status
05_
Check
ODU
internal
communication
db
Light
05
Light
C2
Light
System detects “driven communication
error between master unit and inverter
compressor”.
db
Light
05
Light
C3
Light
System detects “driven communication
error between master unit and inverter
fan”.
db
Light
05
Light
CH
Light IDU/ODU “
diversity exceed 135%"
db
Light
05
Light
CL
Light IDU/ODU “
diversity lower than 50%"
Elimination methods of above errors can be found in Troubleshooting.
Step 10:
step
06 is “Detect outdoor components”
If no error is detected, system will display as below and then start next
step
.