54
——
Cycle
code
Progress code Status code
Meaning
progress
LED1
LED2
LED3
Code Display
status code
Display
status Code
Display
status
06_Detect
outdoor
components
db
Light
06
Light
OC
Light No error is detected in outdoor
components. Start next
step
.
If error is detected, system will stay at current
step
. Error has to be solved manually.
Below is relevant error:
——
Cycle
code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code Display
status code
Display
status Code
Display
status
06_Detect
outdoor
components
db
Light
06
Light
Error
code
Light System detects error in outdoor
components.
Elimination methods of above error can be found in Troubleshooting.
Step11: progress 07 is “Detect indoor components”
If no error is detected, system will display as below and then start next
step
.
——
Cycle
code
Progress code Status code
Meaning
progress
LED1
LED2
LED3
Code Display
status code
Display
status Code
Display
status
07_Detect
indoor
components
db
Light
07
Light
OC
Light No error is detected in indoor
components. Start next
step
.
If error is detected, system will stay at current
step
. Error has to be solved manually.
Below is relevant error:
——
Cycle
code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code Display
status code
Display
status
Code Display
status
07_Detect
indoor
components
db
Light
07
Light
XXXXor
Error
code
Light System detects error in indoor
components.
XXXX is the project no. of the faulted IDU.
After
3s, relevant error code is displayed. For
example, IDU no. 100 has d5 error, then LED3 displays like this: 01 (2s later) 00 (2s later) d5,
and repeat again.
Elimination methods of above error can be found in Troubleshooting.
Step 12: