4.3.2 Manifold
(1) Y-type manifold, See the Fig.34(a). T-type manifold, See the Fig. 34(b)
Fig. 34(a)
Fig. 34(b)
(2) Manifold has serveral pipe sections with different pipe size, which facilitates to match
with various copper pipe. Use pipe cutter to cut in the middle of the pipe section with
different pipe size and deburr as well. See Fig. 35.
Cut from the center
Fig. 35
(3) Y-type manifold can be installed vertically or horizontally. Confirm the position and then
weld the manifold pipe. See the Fig. 36(a). T-type manifold must be installed
horizontally with inclination, see the Fig. 36(b).