24
4.2.5.5 Manifold at indoor unit side
Manifold at indoor unit side can be selected as per total capacity of downstream indoor
unit(s). Refer to the following table.
Fig.30(a)
Fig.30(b)
R410A Refrigerant System
Total capacity of downstream
indoor unit(s)
-
kW
(Btu)
Model
Y-type Manifold
C
<
20.0
(68000)
VEBC01A
20.0
(68000)
≤
C
≤
30.0
(102000)
VEBC01B
30.0
(102000)
<
C
≤
70.0
(238000)
VEBC02A
70.0
(238000)
<
C
≤
135.0
(460000)
VEBC03A
135.0
(460000)
<
C
VEBC04A
T- type Manifold
C
≤
40.0
(136000)
VEBCT4
40.0
(136000)
<
C
≤
68.0
(232000)
VEBCT8A
68.0
<
C
(232000)
VEBCT8B
Lennox
VRF Unit