52
button on the master module for at least 5s to enable
Commissioning Cycle
;
Step 6: Wait. Unit will then start progress 01 and 02; in progress 01, if master unit is not
correctly set, progress 01 will show the following errors:
Cycle
Code
Progress Code
Status Code
Meaning
Progress
LED1
LED2
LED3
Code Display
status
Code Display
status Code
Display
status
01_01 Set
up master
unit:
db
light
01
light
CC
light System doesn’t have master unit.
Reset master unit.
db
light
01
light
CF
light More than 2 master units are set.
Reset master unit.
db
light
01
light
OC
light Master unit is successfully set.
Start next
step
.
According to the above errors, reset the master unit as instructed in Master Unit
Setup SA8_MASTER_S. After reset is finished, start
Commissioning Cycle
again.
In progress 02, if master IDU is not detected, then progress 02 will show the following
errors:
LED1
LED2
LED3
Function code
Display mode
Current
progress
Display mode
Current status
Display mode
db
light
02
light
L7
blink
At this time, all buttons are ineffective. Set master IDU in 1min via
Commission
ing software. If
master IDU is not set in 1min, system will set up a master IDU randomly. After that, system will start
next
step
.
Step 7: in progress 03, the quantity of modules needs to be confirmed manually. Main board
of each module will display:
Cycle
code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
03_Quantity of
ODU
db
light
03
light
Quantity of
modules
blink
If the quantity displayed is the same with actual quantity, then press SW7
confirmation button on the master unit to confirm it. Unit will start next
step
:
Cycle
code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
03_Confirm the
quantity of
ODU
db
light
03
light
OC
light
If the quantity displayed is different from actual quantity, then disconnect power and check
whether communication wire among each module is correctly connected. After the check,
start
Commissioning Cycle