35
Outdoor units
Power Supply
Fuse Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
V/Ph/Hz
A
A
A
VEP075N432K
208V/230V 3~ 60Hz
60
36
60
VEP096N432K
208V/230V 3~ 60Hz
60
38
60
VEP120N432K
208V/230V 3~ 60Hz
60
43
60
VEP132N432K
208V/230V 3~ 60Hz
80
60
80
VEP150N432K
208V/230V 3~ 60Hz
90
65
90
VEP171N432K
208V/230V 3~ 60Hz
110
89
110
VEP192N432K
208V/230V 3~ 60Hz
125
99
125
VEP210N432K
208V/230V 3~ 60Hz
150
113
150
VEP228N432K
208V/230V 3~ 60Hz
60+80
38+60
60+80
VEP246N432K
208V/230V 3~ 60Hz
60+90
38+65
60+90
VEP267N432K
208V/230V 3~ 60Hz
60+110
38+89
60+110
VEP288N432K
208V/230V 3~ 60Hz
60+125
38+99
60+125
VEP306N432K
208V/230V 3~ 60Hz
60+150
38+113
60+150
VEP330N432K
208V/230V 3~ 60Hz
60+150
43+113
60+150
VEP342N432K
208V/230V 3~ 60Hz
80+150
60+113
80+150
VEP360N432K
208V/230V 3~ 60Hz
90+150
65+113
90+150
VEP381N432K
208V/230V 3~ 60Hz
110+150
89+113
110+150
VEP402N432K
208V/230V 3~ 60Hz
125+150
99+113
125+150
VEP420N432K
208V/230V 3~ 60Hz
150+150
113+113
150+150
VEP438N432K
208V/230V 3~ 60Hz
60+90+125
38+65+99
60+90+125
VEP456N432K
208V/230V 3~ 60Hz
60+90+150
38+65+113
60+90+150
VEP480N432K
208V/230V 3~ 60Hz
60+90+150
43+65+113
60+90+150
VEP498N432K
208V/230V 3~ 60Hz
60+125+150
38+99+113
60+125+150
VEP516N432K
208V/230V 3~ 60Hz
60+150+150
38+113+113
60+150+150
VEP540N432K
208V/230V 3~ 60Hz
60+150+150
43+113+113
60+150+150
VEP552N432K
208V/230V 3~ 60Hz
80+150+150
60+113+113
80+150+150
VEP570N432K
208V/230V 3~ 60Hz
90+150+150
65+113+113
90+150+150
VEP591N432K
208V/230V 3~ 60Hz
110+150+150
89+113+113
110+150+150
VEP612N432K
208V/230V 3~ 60Hz
125+150+150
99+113+113
125+150+150
Lennox