65
Error Code
Content
Error Code
Content
P4
Drive PFC protection of compressor
FH
Current sensor of compressor 1 is
abnormal
P5
Over-current protection of inverter
compressor
bP
Malfunction of temperature sensor of
oil-return 2
P6
Drive IPM module protection of
compressor
bU
Malfunction of temperature sensor of
oil return 3
P7
Malfunction of drive temperature
sensor of compressor
bb
Malfunction of temperature sensor of
oil return 4
P8
Drive IPM high temperature
protection of compressor
H0
Malfunction of driving board of fan
P9
Desynchronizing protection of
inverter compressor
H1
Driving board of fan operates
abnormally
PA
Malfunction of drive storage chip of
compressor
H2
Voltage protection of driving board
power of fan
PH
High-voltage protection of
compressor’s drive DC bus bar
H3
Reset protection of driving module of
fan
PC
Malfunction of current detection
circuit drive of compressor
H4
Drive PFC protection of fan
PL
Low voltage protection for DC bus
bar of drive of compressor
H5
Over-current protection of inverter
fan
PE
Phase-lacking of inverter compressor
H6
Drive IPM module protection of fan
PF
Malfunction of charging loop of driven
of compressor
H7
Malfunction of drive temperature
sensor of fan
PJ
Failure startup of inverter
compressor
H8
Drive IPM high temperature
protection of fan
PP
AC current protection of inverter
compressor
H9
Desynchronizing protection of
inverter fan
PU
AC input voltage of drive of inverter
compressor
HA
Malfunction of drive storage chip of
inverter outdoor fan
F0
Main board of ODU is poor
HH
High-voltage protection of fan’s drive
DC bus bar
F1
Malfunction of high-pressure sensor
HC
Malfunction of current detection
circuit of fan drive
F3
Malfunction of low-pressure sensor
HL
Low voltage protection of bus bar of
fan drive
F5
Malfunction of discharge temperature
sensor of compressor 1
HE
Phase-lacking of inverter fan
F6
Malfunction of exit-tube temperature
sensor
HF
Malfunction of charging loop of fan
drive
F7
Malfunction of humidity sensor
HJ
Failure startup of inverter fan
F8
Malfunction of water temperature
sensor
HP
AC current protection of inverter fan
F9
Malfunction of jumper cap
HU
AC input voltage of drive of inverter
fan
FA
Web address of IDU is abnormal
Lennox
VRF Unit