64
Outdoor:
Error Code
Content
Error Code
Content
E0
Malfunction of ODU
FC
Current sensor of compressor 2 is
abnormal
E1
High-pressure protection
FL
Current sensor of compressor 3 is
abnormal
E2
Discharge low-temperature
protection
FE
Current sensor of compressor 4 is
abnormal
E3
Low-pressure protection
FF
Current sensor of compressor 5 is
abnormal
E4
High discharge temperature
protection of compressor
FJ
Current sensor of compressor 6 is
abnormal
J0
Protection for other modules
FP
Malfunction of DC motor
J1
Over-current protection of
compressor 1
FU
Malfunction of casing top
temperature sensor of compressor 1
J2
Over-current protection of
compressor 2
Fb
Malfunction of casing top
temperature sensor of compressor 2
J3
Over-current protection of
compressor 3
Fd
Malfunction of exit tube temperature
sensor of mode exchanger
J4
Over-current protection of
compressor 4
Fn
Malfunction of inlet tube temperature
sensor of mode exchanger
J5
Over-current protection of
compressor 5
b1
Malfunction of outdoor ambient
temperature sensor
J6
Over-current protection for
compressor 6
b2
Malfunction of defrosting
temperature sensor 1
J7
Gas-mixing protection of 4-way valve
b3
Malfunction of defrosting
temperature sensor 2
J8
High pressure ratio protection of
system
b4
Malfunction of liquid temperature
sensor of sub-cooler
J9
Low pressure ratio protection of
system
b5
Malfunction of gas temperature
sensor of sub-cooler
JA
Protection because of abnormal
pressure
b6
Malfunction of inlet tube temperature
sensor of vapor liquid separator
JC
Water flow switch protection
b7
Malfunction of exit tube temperature
sensor of vapor liquid separator
JL
Protection because high pressure is
too low
b8
Malfunction of outdoor humidity
sensor
JE
Oil-return pipe is blocked
b9
Malfunction of gas temperature
sensor of heat exchanger
JF
Oil-return pipe is leaking
bA
Malfunction of oil-return temperature
sensor 1
P0
malfunction of driving board of
compressor
bH
Clock of system is abnormal
P1
Driving board of compressor
operates abnormally
bE
Malfunction of inlet tube temperature
sensor of condenser
P2
Voltage protection of driving board
power of compressor
bF
Malfunction of outlet tube
temperature sensor of condenser
P3
Reset protection of driving module of
compressor
bJ
High-pressure sensor and
low-pressure sensor are connected
reversely
Lennox