GUIDE SPECIFICATIONS

TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump 

/ Page 22

g.

[Accessories:]

1)

[High Pressure Switch Kit: manual reset for system protection from high pressure conditions
resulting from fan failure or blocked/dirty coil.]

2)

[Loss of Charge Kit : SPST, normally closed switch and automatic reset switch mounted on
suction line.]

3)

[Refrigerant Line Kits: Factory cleaned, dried, pressurized and sealed for field fabrication.]

4.

Controls:

a.

Defrost Control:

1)

Solid−state temperature/time control.

2)

Initiates defrost cycle every 30, 60 or 90 minutes of compressor on" time at temperatures below 
42 degrees F (6 degrees C).

3)

Anti−short cycle, timed−off control.

4)

High and low pressure switch monitoring with 5 trip lockout.

b.

[Accessories:]

1)

[Freezestat: senses suction line temperature and cycles compressor off when suction line
temperature falls below 29 degrees F (−2 degrees C) and cycles back on at 58 degrees F (14
degrees C).]

2)

[Low Ambient Control: Available in 2 options based on ambient temperature; for field installation.]

3)

[Mild Weather Kit for field installation to allow heating operation above 75 degrees F (24 degrees
C).]

4)

[Monitor Kit with ambient compensating thermistor and service light thermostat.]

5)

[Outdoor Thermostat Kit to lock out some electric heating elements on indoor units where 2−stage
control is applicable.]

6)

[Thermostat.]

7)

[Time Delay Relay Kit delays indoor blower−off time during cooling cycle.]

5.

Refrigerant Line Connections, Electrical Inlets, Service Valves:

a.

Sweat connection vapor and liquid lines located on cabinet corner.

b.

Fully serviceable and accessible brass service valves.

c.

Full shutoff Vapor valve.

d.

Liquid valve can be front seated to manage refrigerant charge while servicing system.

PART 2.02

PRODUCT SUBSTITUTIONS

A.

Substitutions: No substitutions permitted.

PART 3 EXECUTION

PART 3.01

MANUFACTURER’S INSTRUCTIONS

Specifier Note: Revise article below to suit project requirements and specifier’s practice.

A.

Compliance: Comply with manufacturer’s written data, including product technical bulletins, product catalog installation
instructions and product carton installation instructions.

PART 3.02

EXAMINATION

A.

Site Verification of Conditions: Verify that substrate conditions, which have been previously installed under other sections,
are acceptable for product installation in accordance with manufacturer’s instructions.

PART 3.03

INSTALLATION

A.

Install heat pump in accordance with manufacturer’s instructions and regulations of authorities having jurisdiction.

END OF SECTION

Summary of Contents for TPA036H4

Page 1: ...T P A Y 1 036 h 4 4 n Major Design Sequence A 1st Generation B 2nd Generation Brand Family T T Classt Product Line Unit Type P Heat Pump Outdoor Unit Nominal Cooling Capacity Tons 036 3 Tons 042 3 5...

Page 2: ...ing COP up to 4 04 HSPF Region IV 9 0 3 through 5 tons Three phase power supply Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof Designed for applicatio...

Page 3: ...due low refrigerant charge conditions SPST normally closed switch automatic reset switch mounted on suction line Compressor Scroll Compressor Compressor features high efficiency with uniform suction...

Page 4: ...shed as an aid in troubleshooting Conveniently located in control box OPTIONS Freezestat Installs on or near the discharge line of the indoor coil or on the suction line Senses suction line temperatur...

Page 5: ...E1 Accessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1...

Page 6: ...13 5 6 0 13 7 6 2 16 0 7 8 p Locked Rotor Amps 71 38 88 44 83 1 41 110 52 Power Factor 85 84 83 81 90 92 90 91 Outdoor Fan Motor Full Load Amps 1 8 1 0 1 8 1 0 1 8 1 0 1 8 1 0 Fan Motor Locked Rotor...

Page 7: ...6H4 78 5 77 5 77 5 74 5 69 5 63 5 61 5 79 TPA042H4 76 5 78 78 5 73 5 69 5 63 5 58 5 79 TPA048H4 75 5 78 78 5 75 70 63 5 58 5 80 TPA060H4 75 77 5 77 5 75 5 70 65 65 80 NOTE the octave sound power data...

Page 8: ...0 A ELECTRICAL INLETS LIQUID LINE CONNECTION TOP VIEW BASE SECTION 4 3 8 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed B C A OPTIONAL UNIT ST...

Page 9: ...andlers 34 400 35 400 21 400 14 00 12 00 8 20 7 20 2865 2790 2570 3 72 2 44 4 CBX32M 042 Multi Position 2 49L25 34 400 35 600 21 400 14 00 12 00 8 20 7 20 2865 2785 2575 3 74 2 44 4 CBX32M 036 Multi P...

Page 10: ...00 12 50 8 00 6 70 2830 2910 2655 3 46 2 30 CX34 44 48C 6F 4 G71MPP 60C 090 Factory TXV 35 400 34 600 20 800 14 50 12 50 8 00 6 70 2830 2935 2695 3 46 2 26 CX34 43B 6F 4 G61MPV 36B 045 Factory TXV 35...

Page 11: ...2 00 8 20 6 70 2935 2930 2705 3 48 2 28 CH33 44 48B 2F 4 G61MPV 36B 045 2 49L25 35 200 34 800 21 000 14 00 12 00 8 20 6 70 2935 2920 2700 3 50 2 28 CH33 44 48B 2F 4 G61MPV 36B 070 2 49L25 35 200 34 80...

Page 12: ...3195 2920 3 80 2 62 CX34 60D 6F 4 G71MPP 60D 135 2 49L25 42 500 41 500 26 200 15 00 13 00 9 00 7 70 3400 3190 2915 3 82 2 64 CX34 62D 6F 4 G61MPV 60D 135 2 49L25 42 500 41 500 26 200 15 00 13 00 9 00...

Page 13: ...200 13 00 11 00 7 70 6 70 3820 3275 3025 3 80 2 64 3 CH23 68 2 49L25 42 000 42 500 27 000 13 00 11 00 7 70 6 70 3820 3395 3095 3 66 2 56 3 CH33 43B 2F 2 49L25 Horizontal Indoor Coils Furnaces Horizont...

Page 14: ...2 76 CH23 68 4 G61MPV 60C 090 2 49L25 42 500 42 000 26 600 14 50 12 00 8 50 8 00 3540 3085 2830 4 00 2 76 CH23 68 4 G71MPP 60C 090 2 49L25 42 500 42 000 26 600 14 50 12 00 8 50 8 00 3540 3065 2815 4...

Page 15: ...ry TXV 50 000 47 000 30 200 14 50 12 00 8 20 7 20 4165 3725 3435 3 70 2 58 CX34 62C 6F 4 G71MPP 60C 110 Factory TXV 50 000 47 000 30 200 14 50 12 00 8 20 7 20 4165 3730 3440 3 70 2 58 CX34 62C 6F 4 G6...

Page 16: ...000 14 50 12 00 8 20 7 20 4125 3585 3320 3 84 2 64 CH23 68 4 G60UHV 60C 110 2 91M02 49 500 47 000 30 000 14 50 12 00 8 20 7 20 4125 3575 3310 3 86 2 66 CH23 68 4 G61MPV 60D 135 2 91M02 49 500 47 000 3...

Page 17: ...CH33 50 60C 2F 4 G60UHV 60C 110 2 91M02 57 000 54 500 35 800 13 50 11 00 8 20 7 20 5180 4950 4385 3 22 2 40 CH33 50 60C 2F 4 G61MPV 60C 110 2 91M02 57 000 54 500 35 800 13 50 11 00 8 20 7 20 5180 4950...

Page 18: ...ation Retain Reference Article when specifying products and installation by an industry reference standard If retained list standard s referenced in this section Indicate issuing authority name acrony...

Page 19: ...ipped loose showing final location in assembly d Field wiring diagrams e Dimensions internal and external construction details installation clearances recommended method of installation sizes and loca...

Page 20: ...waste into landfill site demonstrates an inefficient use of natural resources and consumes valuable landfill space 1 Separate waste materials for Reuse And Recycling _____ in accordance with Section...

Page 21: ...urrent and temperature protection d Crankcase heater e Accessories 1 Low Ambient Cut Off nonadjustable switch to prevent compressor operation at outdoor temperatures below 35 degrees F 2 degrees C 2 C...

Page 22: ...ating thermistor and service light thermostat 5 Outdoor Thermostat Kit to lock out some electric heating elements on indoor units where 2 stage control is applicable 6 Thermostat 7 Time Delay Relay Ki...

Page 23: ......

Page 24: ...ittment to quality Specifications Ratings and Dimensions subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause p...

Reviews: