TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump
/ Page 9
ARI RATINGS − INDOOR COIL / AIR HANDLER SUBSTITUTION
Substituting Coils in the ARI Tables
Most R−22 and R−410A indoor coils and air handlers are the same except for the factory installed expansion device. C33
coils can be used in place of the CX34 coils, CB26UH, CB27UH and CB30M air handlers can be used in place of the
CBX26UH, CBX27UH and CBX32M, respectively.
The expansion device is based on the size of the outdoor unit. The factory installed RFC or TXV on the
C33/CB26UH/CB27UH/CB30M must be replaced to correspond to the outdoor unit. The correct TXV’s are:
3−3.5 ton heat pumps
49L25
4−5 ton heat pumps
91M02
Example:
A four−ton heat pump is being installed. The ARI table shows that CBX32M−048 is a matching air handler. A CB30M−51 with
a 91M02 TXV can be used in its place.
UP−FLOW COILS
R−410A
R−22
CX34−31A−6F
=
C33−31A−2
CX34−31B−6F
=
C33−31B−2
CX34−36A−6F
=
C33−36A−2
CX34−36B−6F
=
C33−36B−2
CX34−36C−6F
=
C33−36C−2
CX34−38A−6F
=
C33−38A−2
CX34−38B−6F
=
C33−38B−2
CX34−42B−6F
=
C33−42B−2
CX34−43B−6F
=
C33−43B−2
CX34−43C−6F
=
C33−43C−2
no equivalent
C33−44C−2
CX34−44/48B−6F
=
C33−48B−2
CX34−44/48C−6F
=
C33−48C−2
CX34−49C−6F
=
C33−49C−2
CX34−50/60C−6F
=
C33−50/60C−2
CX34−60D−6F
=
C33−60D−2
CX34−62C−6F
=
C33−62C−2
CX34−62D−6F
=
C33−62D−2
AIR HANDLERS
R−410A
R−22
CBX26UH−036 = CB26UH−036−R
CBX26UH−042 = CB26UH−042−R
CBX26UH−048 = CB26UH−048
CBX26UH−060 = CB26UH−060−R
CBX27UH−036 = CB27UH−036
CBX27UH−042 = CB27UH−042
CBX27UH−048 = CB27UH−048
CBX27UH−060 = CB27UH−060
CBX32M−036 = CB30M−41
CBX32M−042 = CB30M−46
CBX32M−048 = CB30M−51
CBX32M−060 = CB30M−65
CBX32MV all
no equivalent
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh
Efficiency
Total Watts
COP
I d
U it M d l N
Expansion
Cooling
High
Temp
Low
Temp
HSPF
Cool
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooling Temp.
Heating
Temp.
Heating SEER EER
IV
V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA036H4
3 TON
Air Handlers
Air Handlers
34,400
35,400
21,400 14.00 12.00 8.20 7.20 2865 2790 2570 3.72 2.44
4
CBX32M−042 (Multi−Position)
2
49L25
34,400
35,600
21,400 14.00 12.00 8.20 7.20 2865 2785 2575 3.74 2.44
4
CBX32M−036 (Multi−Position)
Factory TXV
34,600
35,200
21,400 14.00 12.00 8.20 7.20 2885 2830 2595 3.64 2.42
5
CBX26UH−037 (Up−Flow / Horizontal)
Factory TXV
34,600
35,400
21,400 14.00 12.00 8.20 7.20 2885 2760 2550 3.76 2.46
4
CBX32MV−036 (Multi−Position)
Factory TXV
34,800
35,000
21,000 15.00 12.50 8.50 7.20 2785 2670 2450 3.84 2.50
4
CBX27UH−036 (Up−Flow / Horizontal)
Factory TXV
35,800
35,200
21,200 15.00 12.50 8.50 7.20 2865 2685 2485 3.84 2.50
4
CBX32MV−048 (Multi−Position)
2
49L25
Up−Flow Indoor Coils
Up−Flow Coils
34,400
35,400
21,600 13.00 11.00 7.70 6.70 3125 2950 2705 3.52 2.34
3
CX34−38A/B−6F
2
49L25
34,600
34,800
21,200 13.00 11.00 7.70 6.70 3145 3130 2855 3.26 2.18
3
CX34−44/48B/C−6F
Factory TXV
35,000
35,000
21,200 13.00 11.00 7.70 6.70 3180 3065 2820 3.34 2.20
3
CX34−50/60C−6F
2
49L25
35,200
35,000
21,200 13.00 11.00 7.70 6.70 3200 3055 2815 3.36 2.20
3
CX34−43B/C−6F
Factory TXV
35,400
35,000
21,200 13.00 11.00 7.70 6.70 3220 3045 2805 3.36 2.22
3
CX34−49C−6F
2
49L25
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings −
95
_
F outdoor air temperature and 80
_
F db/67
_
F wb entering indoor coil air.
High Temperature Heating Ratings −
47
_
F db/43
_
F wb outdoor air temperature and 70
_
F db entering indoor coil air.
Low Temperature Heating Ratings −
17
_
F db/15
_
F wb outdoor air temperature and 70
_
F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (
58M81
) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.