background image

TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump 

/ Page 16

ARI RATINGS

ARI Standard 210/240 Ratings

Capacity − Btuh

Efficiency

Total Watts

COP

I d

U it M d l N

Expansion

Cooling

High

Temp

Low

Temp

HSPF

Cool

High Low High Low

Indoor Unit Model No.

Expansion
Device

Cooling Temp.

Heating

Temp.

Heating SEER EER

IV

V

Cool

High

Heat

Low

Heat

High

Heat

Low

Heat

TPA048H4

4 TON

Horizontal Indoor Coils

Horizontal Coils

48,000

46,500

30,400 13.00 11.00 7.70 6.70 4365 4005 3675 3.40 2.42

CH33−60D−2F

91M02

48,500

47,000

30,400 13.00 11.00 7.70 6.70 4410 3995 3655 3.44 2.44

CH33−62D−2F

91M02

48,500

47,000

30,400 13.00 11.00 7.70 6.70 4410 3965 3645 3.48 2.44

CH33−50/60C−2F

91M02

49,000

48,000

30,800 13.00 11.00 7.70 6.70 4455 3775 3510 3.72 2.56

CH23−68

91M02

Horizontal Indoor Coils + Furnaces

Horizontal Coils + Furnaces

48,500

46,000

29,600 14.50 12.00 8.20 7.20 4040 3800 3465 3.54 2.50 CH33−60D−2F

G60UHV−60D−135

91M02

48,500

46,000

29,800 14.00 12.00 8.20 7.20 4040 3835 3505 3.52 2.48 CH33−60D−2F

G61MPV−60D−135

91M02

48,500

46,000

29,800 14.00 12.00 8.20 7.20 4040 3835 3505 3.52 2.48 CH33−60D−2F

G71MPP−60D−135

2

 

91M02

49,000

46,000

29,600 14.50 12.00 8.20 7.20 4085 3790 3445 3.56 2.52 CH33−62D−2F

G60UHV−60D−135

91M02

49,000

46,000

29,800 14.00 12.00 8.20 7.20 4085 3825 3485 3.52 2.50 CH33−62D−2F

G61MPV−60D−135

91M02

49,000

46,000

29,800 14.00 12.00 8.20 7.20 4085 3825 3485 3.52 2.50 CH33−62D−2F

G71MPP−60D−135

2

 

91M02

49,000

46,500

30,000 14.00 12.00 8.20 7.20 4085 3820 3505 3.56 2.50 CH33−50/60C−2F

G60UHV−60C−090

91M02

49,000

46,500

30,000 14.00 12.00 8.20 7.20 4085 3840 3520 3.54 2.50 CH33−50/60C−2F

G60UHV−60C−110

91M02

49,000

46,500

30,200 14.00 12.00 8.20 7.20 4085 3880 3560 3.52 2.48 CH33−50/60C−2F

G61MPV−60C−090

91M02

49,000

46,500

30,200 14.00 12.00 8.20 7.20 4085 3880 3560 3.52 2.48 CH33−50/60C−2F

G71MPP−60C−090

2

 

91M02

49,000

46,500

30,200 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CH33−50/60C−2F

G61MPV−60C−110

91M02

49,000

46,500

30,200 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CH33−50/60C−2F

G71MPP−60C−110

2

 

91M02

49,000

46,500

30,200 14.00 12.00 8.20 7.20 4085 3880 3560 3.52 2.48 CH33−50/60C−2F

G61MPV−60C−111

91M02

49,000

47,000

30,400 14.00 12.00 8.20 7.20 4085 3915 3600 3.52 2.48 CH33−50/60C−2F

G61MPV−60C−091

91M02

49,500

47,000

30,000 14.50 12.00 8.20 7.20 4125 3565 3315 3.86 2.66 CH23−68

G60UHV−60C−090

91M02

49,500

47,000

30,000 14.50 12.00 8.20 7.20 4125 3585 3320 3.84 2.64 CH23−68

G60UHV−60C−110

91M02

49,500

47,000

30,000 14.50 12.00 8.20 7.20 4125 3575 3310 3.86 2.66 CH23−68

G61MPV−60D−135

91M02

49,500

47,000

30,000 14.50 12.00 8.20 7.20 4125 3575 3310 3.86 2.66 CH23−68

G71MPP−60D−135

2

 

91M02

49,500

47,000

30,200 14.50 12.00 8.20 7.20 4125 3625 3360 3.80 2.64 CH23−68

G61MPV−60C−090

91M02

49,500

47,000

30,200 14.50 12.00 8.20 7.20 4125 3625 3360 3.80 2.64 CH23−68

G71MPP−60C−090

2

 

91M02

49,500

47,000

30,200 14.50 12.00 8.20 7.20 4125 3610 3345 3.82 2.64 CH23−68

G61MPV−60C−110

91M02

49,500

47,000

30,200 14.50 12.00 8.20 7.20 4125 3610 3345 3.82 2.64 CH23−68

G71MPP−60C−110

2

 

91M02

49,500

47,500

30,200 14.50 12.00 8.20 7.20 4125 3625 3360 3.84 2.64 CH23−68

G61MPV−60C−111

91M02

49,500

47,500

30,400 14.00 12.00 8.20 7.20 4125 3665 3410 3.80 2.62 CH23−68

G61MPV−60C−091

91M02

50,000

47,000

29,800 15.00 13.00 9.00 7.50 3845 3530 3290 3.90 2.66 CH23−68

G60UHV−60D−135

91M02

TPA060H4

5 TON

Air Handlers

Air Handlers

56,000

55,000

35,600 14.00 11.50 8.20 7.50 4870 4640 4135 3.48 2.52

CBX32MV−048 (Multi−Position)

Factory TXV

56,500

54,500

35,400 14.00 11.50 8.20 7.20 4915 4840 4305 3.30 2.40

CBX32MV−068 (Multi−Position)

Factory TXV

56,500

55,000

35,800 14.00 11.50 8.20 7.50 4915 4665 4195 3.46 2.50

CBX32M−060 (Multi−Position)

Factory TXV

56,500

55,000

35,800 14.00 11.50 8.20 7.50 4915 4680 4215 3.44 2.48

CBX32MV−060 (Multi−Position)

Factory TXV

58,500

55,000

35,800 14.00 12.00 8.20 7.50 4875 4610 4120 3.50 2.54

5

 CBX26UH−060 (Up−Flow / Horizontal)

Factory TXV

59,000

55,500

36,000 15.00 12.50 8.50 7.70 4720 4585 4055 3.54 2.60

CBX27UH−060 (Up−Flow / Horizontal)

Factory TXV

NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).

1

Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;

Cooling Ratings − 

95

_

F outdoor air temperature and 80

_

F db/67

_

F wb entering indoor coil air.

High Temperature Heating Ratings − 

47

_

F db/43

_

F wb outdoor air temperature and 70

_

F db entering indoor coil air.

Low Temperature Heating Ratings − 

17

_

F db/15

_

F wb outdoor air temperature and 70

_

F db entering indoor coil air.

2

Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).

3

Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (

58M81

) is recommend for field installation.

4

Blower control must be set for a time−off blower delay.

5

Most popular air handler combination.

Summary of Contents for TPA036H4

Page 1: ...T P A Y 1 036 h 4 4 n Major Design Sequence A 1st Generation B 2nd Generation Brand Family T T Classt Product Line Unit Type P Heat Pump Outdoor Unit Nominal Cooling Capacity Tons 036 3 Tons 042 3 5...

Page 2: ...ing COP up to 4 04 HSPF Region IV 9 0 3 through 5 tons Three phase power supply Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof Designed for applicatio...

Page 3: ...due low refrigerant charge conditions SPST normally closed switch automatic reset switch mounted on suction line Compressor Scroll Compressor Compressor features high efficiency with uniform suction...

Page 4: ...shed as an aid in troubleshooting Conveniently located in control box OPTIONS Freezestat Installs on or near the discharge line of the indoor coil or on the suction line Senses suction line temperatur...

Page 5: ...E1 Accessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1...

Page 6: ...13 5 6 0 13 7 6 2 16 0 7 8 p Locked Rotor Amps 71 38 88 44 83 1 41 110 52 Power Factor 85 84 83 81 90 92 90 91 Outdoor Fan Motor Full Load Amps 1 8 1 0 1 8 1 0 1 8 1 0 1 8 1 0 Fan Motor Locked Rotor...

Page 7: ...6H4 78 5 77 5 77 5 74 5 69 5 63 5 61 5 79 TPA042H4 76 5 78 78 5 73 5 69 5 63 5 58 5 79 TPA048H4 75 5 78 78 5 75 70 63 5 58 5 80 TPA060H4 75 77 5 77 5 75 5 70 65 65 80 NOTE the octave sound power data...

Page 8: ...0 A ELECTRICAL INLETS LIQUID LINE CONNECTION TOP VIEW BASE SECTION 4 3 8 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed B C A OPTIONAL UNIT ST...

Page 9: ...andlers 34 400 35 400 21 400 14 00 12 00 8 20 7 20 2865 2790 2570 3 72 2 44 4 CBX32M 042 Multi Position 2 49L25 34 400 35 600 21 400 14 00 12 00 8 20 7 20 2865 2785 2575 3 74 2 44 4 CBX32M 036 Multi P...

Page 10: ...00 12 50 8 00 6 70 2830 2910 2655 3 46 2 30 CX34 44 48C 6F 4 G71MPP 60C 090 Factory TXV 35 400 34 600 20 800 14 50 12 50 8 00 6 70 2830 2935 2695 3 46 2 26 CX34 43B 6F 4 G61MPV 36B 045 Factory TXV 35...

Page 11: ...2 00 8 20 6 70 2935 2930 2705 3 48 2 28 CH33 44 48B 2F 4 G61MPV 36B 045 2 49L25 35 200 34 800 21 000 14 00 12 00 8 20 6 70 2935 2920 2700 3 50 2 28 CH33 44 48B 2F 4 G61MPV 36B 070 2 49L25 35 200 34 80...

Page 12: ...3195 2920 3 80 2 62 CX34 60D 6F 4 G71MPP 60D 135 2 49L25 42 500 41 500 26 200 15 00 13 00 9 00 7 70 3400 3190 2915 3 82 2 64 CX34 62D 6F 4 G61MPV 60D 135 2 49L25 42 500 41 500 26 200 15 00 13 00 9 00...

Page 13: ...200 13 00 11 00 7 70 6 70 3820 3275 3025 3 80 2 64 3 CH23 68 2 49L25 42 000 42 500 27 000 13 00 11 00 7 70 6 70 3820 3395 3095 3 66 2 56 3 CH33 43B 2F 2 49L25 Horizontal Indoor Coils Furnaces Horizont...

Page 14: ...2 76 CH23 68 4 G61MPV 60C 090 2 49L25 42 500 42 000 26 600 14 50 12 00 8 50 8 00 3540 3085 2830 4 00 2 76 CH23 68 4 G71MPP 60C 090 2 49L25 42 500 42 000 26 600 14 50 12 00 8 50 8 00 3540 3065 2815 4...

Page 15: ...ry TXV 50 000 47 000 30 200 14 50 12 00 8 20 7 20 4165 3725 3435 3 70 2 58 CX34 62C 6F 4 G71MPP 60C 110 Factory TXV 50 000 47 000 30 200 14 50 12 00 8 20 7 20 4165 3730 3440 3 70 2 58 CX34 62C 6F 4 G6...

Page 16: ...000 14 50 12 00 8 20 7 20 4125 3585 3320 3 84 2 64 CH23 68 4 G60UHV 60C 110 2 91M02 49 500 47 000 30 000 14 50 12 00 8 20 7 20 4125 3575 3310 3 86 2 66 CH23 68 4 G61MPV 60D 135 2 91M02 49 500 47 000 3...

Page 17: ...CH33 50 60C 2F 4 G60UHV 60C 110 2 91M02 57 000 54 500 35 800 13 50 11 00 8 20 7 20 5180 4950 4385 3 22 2 40 CH33 50 60C 2F 4 G61MPV 60C 110 2 91M02 57 000 54 500 35 800 13 50 11 00 8 20 7 20 5180 4950...

Page 18: ...ation Retain Reference Article when specifying products and installation by an industry reference standard If retained list standard s referenced in this section Indicate issuing authority name acrony...

Page 19: ...ipped loose showing final location in assembly d Field wiring diagrams e Dimensions internal and external construction details installation clearances recommended method of installation sizes and loca...

Page 20: ...waste into landfill site demonstrates an inefficient use of natural resources and consumes valuable landfill space 1 Separate waste materials for Reuse And Recycling _____ in accordance with Section...

Page 21: ...urrent and temperature protection d Crankcase heater e Accessories 1 Low Ambient Cut Off nonadjustable switch to prevent compressor operation at outdoor temperatures below 35 degrees F 2 degrees C 2 C...

Page 22: ...ating thermistor and service light thermostat 5 Outdoor Thermostat Kit to lock out some electric heating elements on indoor units where 2 stage control is applicable 6 Thermostat 7 Time Delay Relay Ki...

Page 23: ......

Page 24: ...ittment to quality Specifications Ratings and Dimensions subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause p...