Page 27

G−Flame Signal

A  microamp DC meter is needed to check the flame signal
on the ignition control.
Flame (microamp) signal is an electrical current which passes
from the furnace control through the sensor during unit opera-
tion. Current passes from the sensor through the flame to
ground to complete a safety circuit.

To Measure Flame Signal − Ignition Control:

A transducer (Part
#78H5401 available from
Lennox Repair Parts) is
required to measure flame
signal if meter used will not
read a low micro amp sig-
nal. Seefigure20. The
transducer converts mi-
croamps to volts on a 1:1 conversion.  See table15 for flame
signal . A digital readout meter must be used. The transduc-
er plugs into most meters. See figure 21 for proper use of
transducer.
1 − Set  the  volt  meter  to  the  DC  voltage  scale.  Insert

transducer into the VDC and common inputs. Ob-
serve correct polarities. Failure to do so results in
negative (−) values.

2 − Turn off supply voltage to control.
3 − Disconnect ignition control flame sensor wire from the

flame sensor.

4 − Connect (−) lead of the transducer to flame sensor.
5 − Connect (+) lead of transducer to the ignition control sen-

sor wire.

6 − Turn supply voltage on and close thermostat contacts to

cycle system.

7 − When main burners are in operation for two minutes, take

reading. Remember 1 DC volt = 1 DC microamp.

TABLE 15

Flame Signal in Microamps

Control

Normal

Low

Drop Out

56L84,
10M93

 0.18

0.16 − 0.17

 0.15

78M47

100973−01

 1.5

0.5 − 1.4

 0.4

SET DIAL TO

MEASURE VDC

(+)

(−)

(−) TO

FLAME

SENSOR

NOTE−MUST USE DIGITAL METER

RED COLLAR

INDICATES

POSITIVE

LEAD

(+) TO

IGNITION

CONTROL

SENSOR

WIRE

FIGURE 21

WARNING

Fire and explosion hazard.
These instructions MUST be followed exactly.
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.

V−TYPICAL OPERATING CHARACTERISTICS

A−Blower Operation and Adjustment

NOTE− The following is a generalized procedure and
does not apply to all thermostat controls.

1 − Blower operation is dependent on thermostat control

system.

2 − Generally, blower operation is set at thermostat sub-

base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand or runs continuously while
heating or cooling circuit cycles.

3 − Depending on the type of indoor thermostat, blower

and entire unit will be off when the system switch is in
OFF position.

B−Temperature Rise

Temperature rise for G40UH(X) units depends on unit in-
put, blower speed, blower horsepower and static pressure
as marked on the unit rating plate. The blower speed must
be set for  unit operation within the range of  TEMP. RISE

°

F" listed on the unit rating plate.

To Measure Temperature Rise:

1 − Place plenum thermometers in the supply and return air

plenums. Locate supply air thermometer in the first hori-
zontal run of the plenum where it will not pick up radiant
heat from the heat exchanger.

2 − Set thermostat to highest setting.
3 − After plenum thermometers have reached their high-

est and steadiest readings, subtract the two readings.
The difference should be in the range listed on the unit
rating Plate. If the temperature is too low, decrease
blower speed. If temperature is too high, first check the
firing rate. Provided the firing rate is acceptable, in-
crease blower speed to reduce temperature. To
change blower speed taps see the Blower Speed Taps
section in this manual.

C−External Static Pressure

1 − Tap locations shown in figure 22.
2 − Punch a 1/4" diameter hole

in supply and return air ple-
nums. Insert manometer
hose flush with inside edge
of hole or insulation. Seal
around the hose with perma-
gum. Connect the zero end
of the manometer to the dis-
charge (supply) side of the system. On ducted sys-
tems, connect the other end of manometer to the return
duct as above. For systems with non−ducted returns,
leave the other end of the manometer open to the at-
mosphere.

Summary of Contents for G40UHX Series

Page 1: ...not supersede or replace local or state codes In the absence of local or state codes the guidelines and procedures outlined in this manual except where noted are recommended only and do not constitut...

Page 2: ...35 G40UH 60D 155 g Performance Low NOx Model No 60C 110X Input Btuh 110 000 110 000 110 000 132 000 132 000 154 000 Output Btuh 90 200 88 500 89 400 106 900 106 900 124 700 2 AFUE 80 0 80 0 80 0 80 0...

Page 3: ...33 62D 2F Horizontal CH33 36C 2F CH33 48C 2F CH33 50 60C 2F CH33 60D 2F CH33 62D 2F Electrical characteristics 120 volts 60 hertz 1 phase less than 12 amps OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA A...

Page 4: ...with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G40UH 24A 070 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Externa...

Page 5: ...0 930 440 405 780 370 335 0 40 100 1285 605 610 1140 540 475 900 425 390 745 350 325 0 50 125 1215 575 580 1080 510 450 865 410 375 705 335 310 0 60 150 1150 545 560 1015 480 430 810 380 355 655 310 2...

Page 6: ...555 1265 595 459 40 100 1820 860 699 1670 790 611 1470 695 525 1255 590 443 50 125 1740 820 664 1600 755 575 1420 670 496 1215 575 414 60 150 1635 770 624 1530 720 544 1350 635 464 1175 555 400 70 17...

Page 7: ...t with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G40UH 48C 135 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Extern...

Page 8: ...filter not furnished field provided in place Also see Filter Air Resistance table G40UH 60C 110 1 2 3 with 3 4 hp motor PERFORMANCE Single Side Return Air Air volumes in bold require field fab ricated...

Page 9: ...le filter not furnished field provided in place Also see Filter Air Resistance table G40UH 60C 110 with 1 hp motor PERFORMANCE Single Side Return Air Air volumes in bold require field fabricated trans...

Page 10: ...able filter not furnished field provided in place Also see Filter Air Resistance table G40UH 60D 135 1 2 3 with 3 4 hp motor PERFORMANCE Single Side Return Air Air volumes in bold require field fab ri...

Page 11: ...5 791 1545 730 656 30 75 2235 1055 1234 2045 965 914 1820 860 774 1540 725 642 40 100 2160 1020 1240 1985 935 886 1800 850 755 1540 725 628 50 125 2065 975 1170 1925 910 863 1745 825 726 1535 725 614...

Page 12: ...s Watts 00 0 2670 1260 1386 2325 1095 1048 1970 930 857 1700 800 706 10 25 2580 1215 1342 2320 1095 1045 1965 925 842 1690 795 696 20 50 2510 1185 1311 2255 1065 985 1960 925 817 1640 775 662 30 75 24...

Page 13: ...pressure regulator setting Manifold Pressure Outlet in w g kPa FUEL ALTITUDE ft m FUEL 0 10 000 0 3048 Natural Gas 3 5 87 LPG Propane 10 0 2 49 HIGH ALTITUDE G40UH 1 1 High Altitude Orifice Kit Natur...

Page 14: ...Orifices Ignitor Bracket Burner Bottom Shield Limit Shield Secondary Limit as required NOx Units Only G40UH X PARTS ARRANGEMENT FIGURE 1 Gas Manifold 135 and 155 kBtuh units only Flame rollout switch...

Page 15: ...GURE 3 G40UH X HEATING COMPONENTS COMBUSTION AIR INDUCER PROVE SWITCH PRIMARY LIMIT PRIMARY LIMIT SHIELD GAS VALVE ROLLOUT SWITCHES MANIFOLD BURNER ASSEMBLY NOx Insert NOx Units Only HEAT EXCHANGER FL...

Page 16: ...NG Shock hazard Disconnect power before servicing Control is not field repairable If control is inoperable sim ply replace entire control Can cause injury or death Unsafe operation will result if repa...

Page 17: ...f 35 seconds After a total of five trials for ignition including the initial trial the control goes into Watchguard Flame Failure mode After a 60 min ute reset period the control will begin the igniti...

Page 18: ...OFF Circuit board failure or control wired incorrectly OFF ON y FAST FLASH SLOW FLASH Main power polarity reversed Switch line and neutral SLOW FLASH FAST FLASH Low flame signal See Table 15 for flam...

Page 19: ...nal designations See table 4 for troubleshooting diagnostic codes The mini nitride ignitor is made from a non porous high strength proprietary ce ramic material that provides long life and trouble fre...

Page 20: ...ote the supply air temperature at the instant the blower is de energized Adjust the fan off delay to achieve a supply air temperature between 90 110 at the instant the blower is de ener gized Longer d...

Page 21: ...ion air inducer may be rotated clockwise or counterclockwise by 90 to allow for vertical vent discharge in a horizontal application Remove the four mounting screws rotate the assembly assembly consist...

Page 22: ...HP motors have 2 flat sides and are matched with blower wheels with 2 set screws 10 Primary Limit Control S10 The primary limit S10 on G40UH X units is located in the heating vestibule panel When exc...

Page 23: ...3 Combustion Air Inducer Proving Switch S18 G40UH X series units are equipped with a combustion air proving switch located on the combustion air inducer orifice bracket The switch is connected to the...

Page 24: ...utes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruc tions If you do not smell gas go to next step 8 Honeyw...

Page 25: ...ck gas line pressure with unit firing at maximum rate Low pres sure may result in erratic operation or underfire High pres sure can result in permanent damage to gas valve or over fire See table 12 fo...

Page 26: ...ate reading shut off all other gas appliances connected to meter IMPORTANT For safety shut unit off and remove manometer as soon as an accurate reading has been obtained Take care to replace pressure...

Page 27: ...S A Blower Operation and Adjustment NOTE The following is a generalized procedure and does not apply to all thermostat controls 1 Blower operation is dependent on thermostat control system 2 Generally...

Page 28: ...ning furnace Cleaning the heat exchanger requires a steel spring snake a reversible drill and a vacuum cleaner The steel spring snake may be constructed by purchasing a 4 ft long by 1 4 diameter steel...

Page 29: ...section DO NOT BEND 15 Replace burner manifold assembly onto vestibule panel 16 Reconnect wires to pressure switch roll out switch gas valve and combustion air inducer Refer to unit wiring diagram 17...

Page 30: ...or control goes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control A92 energizes ignitor A 20 sec ond warm up period begins 5 Gas valve op...

Page 31: ...SECOND GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLA...

Page 32: ...GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Seque...

Page 33: ...LOWER OFF HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WAT...

Page 34: ...D SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY COOLING SPEED EAC H TERM ENERGIZED COMPRESSO...

Page 35: ...S ENERGIZED THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL H SPEED EAC H TERM REMAINS ON THERMOSTAT OPENS CONTROL G ENERGIZES SYSTEM FAN AT HEAT...

Page 36: ...nto 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 Ignition control A92 energizes ignitor A 20 second warm up period begins 5 Gas valve opens for a 4 second...

Page 37: ...INIMUM OF 1 SECOND GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED...

Page 38: ...DE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILURE CODE IS 60 MINUTE RESET PERIOD COMPLETE YES 4 SECONDS YES HAS CONTROL RESET IGNITION SEQUENCE FO...

Page 39: ...ROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS SYSTEM FAN AND EA...

Page 40: ...ED THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G EN...

Page 41: ...the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace code LED 1 O 1 2 2 Roll out switch failure ACTION 1 Check continuity across roll out switch Replace...

Page 42: ...IT FAILS TO FIRE IN THE HEATING MODE COMBUSTION AIR BLOWER DOES NOT ENERGIZE Condition Possible Cause Corrective Action Comments 2 1 Unit operates with a cooling or contin uous fan demand Combustion a...

Page 43: ...a heating demand Diagnostic lights flash the pressure switch failure code 2 5 minutes after heating demand 3 1 2 Prove switch does not close due to obstructions in the pressure lines ACTION 1 Remove...

Page 44: ...e switch code LED 1 Off LED 2 Slow Flash 5 1 1 Low pressure differential at the prove switch ACTION 1 Check for restricted exhaust vent Remove all blockage ACTION 2 Check for proper vent sizing See in...

Page 45: ...exchanger openings Cor rect the location of the burners if necessary 5 4 Combustion air inducer energizes with a heating demand B li ht hl d th it 5 4 1 Poor Venting ACTION 1 Check vent pipe and remo...

Page 46: ...tion Comments 7 0 Indoor blower fails to operate in continuous fan cooling or heating mode 7 1 1 Miswiring of furnace or improper con nections at control or indoor blower motor ACTION 1 Correct wiring...

Reviews: