FILTER AIR RESITANCE
cfm (L/s)
in. w.g. (Pa)
0 (0)
0.00 (0)
200 (95)
0.01 (0)
400 (190)
0.03 (5)
600 (285)
0.04 (10)
800 (380)
0.06 (15)
1000 (470)
0.09 (20)
1200 (565)
0.12 (30)
1400 (660)
0.15 (35)
1600 (755)
0.19 (45)
1800 (850)
0.23 (55)
2000 (945)
0.27 (65)
2200 (1040)
0.33 (80)
2400 (1130)
0.38 (95)
2600 (1225)
0.44 (110)
HIGH ALTITUDE
All −1 to −14
models − Pressure regulator adjustment may be
required depending on altitude. See below for proper pressure
regulator setting.
Manifold Pressure (Outlet) in. w.g. (kPa)
ALTITUDE ft. (m)
FUEL
0−4500
(0−1372)
4501−5500
(1373−1676)
5501−6500
(1677−1981)
6501−7500
(1982−2286)
Natural Gas
3.5 (.87)
3.3 (.82)
3.2 (.80)
3.1 (.77)
LPG/Propane
10.0 (2.49)
All −15 and later models
− Pressure regulator adjustment is
not rquired. See below for proper pressure regulator setting.
Manifold Pressure (Outlet) in. w.g. (kPa)
FUEL
ALTITUDE ft. (m)
FUEL
0 − 10,000 (0 − 3048)
Natural Gas
3.5 (.87)
LPG/Propane
10.0 (2.49)
HIGH ALTITUDE
G40UH−1
1
High Altitude
Orifice Kit
Natural Gas Only
High Altitude Prove
Switch Kit
LPG/Propane Kit
G40UH−1
to −14
Natural Gas Only
4501−7500 ft.
(1373− 2236m)
7501−10,000 ft.
(2287 − 3048m)
0−7500 ft.
(0 − 2286m)
7501−10,000 ft.
(2286 − 3048m)
−045−
−070
47M82
56L32
56L32
45L60
47M81
−090
47M82
49L90
15M22
45L60
47M81
−110
47M82
49L90
15M22
45L60
47M81
−135
47M82
49L90
15M22
45L60
47M81
−155
47M82
49L90
15M22
45L60
47M81
G40UH−15
1
High Altitude
Orifice Kit
Natural Gas Only
High Altitude Pressure
Switch Kit
LPG/Propane Kit
G40UH−15
and later
Natural Gas Only
4501−7500 ft.
(1373 − 2286m)
7501−10,000 ft.
(2287 − 3048m)
0−7500 ft.
(0 − 2286m)
7501−10,000 ft.
(2286 − 3048m)
all models
59M17
NO CHANGE
56L32
25W20
25W21
1
Required for proper operation at altitudes from 7501 to 10,000 ft.