Page 5
BLOWER DATA
G40UH−36A−045 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
1480
615
1300
545
1100
460
930
385
0.05
1465
605
1290
530
1100
450
930
380
0.10
1445
585
1280
520
1100
445
930
370
0.15
1440
585
1275
505
1095
435
935
365
0.20
1415
570
1260
495
1090
425
935
360
0.25
1400
560
1250
485
1090
420
930
355
0.30
1375
545
1235
470
1075
410
930
350
0.40
1320
520
1195
450
1060
390
915
330
0.50
1265
495
1160
430
1020
375
890
320
0.60
1210
475
1105
410
975
350
840
295
0.70
1135
450
1045
380
910
325
775
280
0.80
1025
415
915
345
810
300
720
265
0.90
885
380
815
320
725
270
640
240
NOTE − All air data is measured external to unit with 1 in. cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G40UH−36A−070 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1500
710
705
1290
610
565
985
465
455
830
390
375
0.05
12
1475
695
695
1275
600
555
980
465
445
820
385
365
0.10
25
1450
685
680
1255
590
545
970
460
440
810
380
360
0.15
37
1425
675
670
1240
585
535
965
455
430
805
380
355
0.20
50
1400
660
655
1225
580
525
955
450
425
795
375
350
0.25
62
1370
645
645
1205
570
510
945
445
415
790
375
345
0.30
75
1340
630
630
1180
555
500
930
440
405
780
370
335
0.40
100
1285
605
610
1140
540
475
900
425
390
745
350
325
0.50
125
1215
575
580
1080
510
450
865
410
375
705
335
310
0.60
150
1150
545
560
1015
480
430
810
380
355
655
310
290
0.70
175
1060
500
535
940
445
405
730
345
330
585
275
270
0.80
200
955
450
515
800
375
370
655
310
305
480
225
260
0.90
225
785
370
475
605
285
325
585
275
270
410
195
255
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G40UH−36B−090 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1500
710
720
1255
590
595
1040
490
460
900
425
370
0.05
12
1485
700
705
1250
590
580
1040
490
450
895
420
365
0.10
25
1465
690
685
1240
585
570
1035
490
445
890
420
360
0.15
37
1450
685
675
1235
585
555
1035
490
440
885
420
355
0.20
50
1435
675
660
1225
580
545
1030
485
435
880
415
350
0.25
62
1420
670
645
1215
575
530
1025
485
425
875
415
345
0.30
75
1400
660
630
1200
565
520
1020
480
415
870
410
340
0.40
100
1345
635
595
1170
550
495
1000
470
400
855
405
330
0.50
125
1300
615
575
1135
535
475
965
455
380
830
390
300
0.60
150
1235
585
545
1080
510
445
930
440
360
780
370
290
0.70
175
1165
550
510
1020
480
415
870
410
340
740
350
280
0.80
200
1080
510
480
940
445
385
800
380
315
670
315
260
0.90
225
985
465
445
840
395
355
710
335
290
600
285
245
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.