8.Flame Rollout Switches (S47)

Flame rollout switch is a high temperature limit located on
top of the burner box (135 and 155 Btuh units− rollout
switches are located on inner sides of burner box).  See
heating components figure 3. Each furnace is equipped
with two identical switches. One switch is located over the
leftmost burner and the other switch is located over the
rightmost burner. The limit is a N.C. SPST manual-reset
limit connected in series with the ignition control A92. When
S47 senses rollout, the ignition control immediately stops
ignition and closes the gas valve. If unit is running and
flame rollout is detected, the gas valve will close and igni-
tion control will be disabled.  Rollout can be caused by a
blocked heat exchanger, flue or lack of combustion air. The
switch is factory set and cannot be adjusted. See table 9. The
switch can be manually reset. To manually reset a tripped
switch, push the reset button located on the control.

TABLE 9

BTUH INPUT

Rollout Switch Setpoint

−045

−070

250° F

−090

250° F

−110

−135

200° F

−155

200° F

FIGURE 14

SUPPLY AIR BLOWER

AND SECONDARY LIMIT (S)

To Remove Blower From Unit: Disconnect Power, Remove Control

Box, Remove Bolts and Unplug Motor Wires From Control Board.

Then Slide Out Front of Unit.

SECONDARY

 LIMIT (S)

CAPACITOR

MOTOR/BLOWER

 ASSEMBLY

Left Side

Right Side

9.Blower Motors and Capacitors

All G40UH(X) units use direct drive blower motors. All mo-
tors are 120V permanent split capacitor motors to ensure
maximum efficiency. Ratings for capacitors  will be on motor
nameplate.

NOTE − The shaft on 1 HP motors have 2 flat sides and
are matched with blower wheels with 2 set screws.

10.Primary Limit Control (S10)

The primary limit (S10) on G40UH(X) units is located in the
heating vestibule panel.  When excess heat is sensed in the
heat exchanger, the limit will open. If the limit is open, the fur-
nace control energizes the supply air blower and closes the
gas valve. The limit automatically resets when unit tempera-
ture returns to normal. The switch must reset within three min-
utes or SureLight board will  go into Watch guard  for one hour.
The switch is factory set and cannot be adjusted. The switch
may have a different setpoint for each unit model number. If
limit switch must be replaced, refer to Lennox Repair Parts
handbook.

11.Secondary Limit Controls (S21)

The secondary limit (S21) on G40UH(X)  (−24A−045 will not
have a secondary limit) units is located in the blower compart-
ment in the back side of the blower housing. See figure 14.
Table 10 and the blower speed chart on the wiring  diagram
show secondary  limit quantities per unit. When excess heat is
sensed in the  blower compartment, the limit will open. If the
limit is open, the furnace control energizes the supply air blow-
er and closes the gas valve. The limit automatically resets
when unit temperature returns to normal. G40UH−1  through −6
units use a surface type limit factory set to open at 125°F.
G40UH−7 units and later, use an airstream type limit factory
set to open at 135°. The secondary limit cannot be adjusted.
 

TABLE 10

G40UH

UNIT

Quantity

LeftSide

Right Side

24A−045

0

No

No

24A−070

2

Yes

Yes

36A−045

2

Yes

Yes

36A−070

2

Yes

Yes

36B−090

1

No

Yes

36C−110

1

No

Yes

48B−070

2

Yes

Yes

48B−090

2

Yes

Yes

48C−110

1

No

Yes

48C−135

2

Yes

Yes

60C−110

1

No

Yes

60D−135

2

Yes

Yes

60D−155

2

Yes

Yes

Summary of Contents for G40UHX Series

Page 1: ...not supersede or replace local or state codes In the absence of local or state codes the guidelines and procedures outlined in this manual except where noted are recommended only and do not constitut...

Page 2: ...35 G40UH 60D 155 g Performance Low NOx Model No 60C 110X Input Btuh 110 000 110 000 110 000 132 000 132 000 154 000 Output Btuh 90 200 88 500 89 400 106 900 106 900 124 700 2 AFUE 80 0 80 0 80 0 80 0...

Page 3: ...33 62D 2F Horizontal CH33 36C 2F CH33 48C 2F CH33 50 60C 2F CH33 60D 2F CH33 62D 2F Electrical characteristics 120 volts 60 hertz 1 phase less than 12 amps OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA A...

Page 4: ...with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G40UH 24A 070 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Externa...

Page 5: ...0 930 440 405 780 370 335 0 40 100 1285 605 610 1140 540 475 900 425 390 745 350 325 0 50 125 1215 575 580 1080 510 450 865 410 375 705 335 310 0 60 150 1150 545 560 1015 480 430 810 380 355 655 310 2...

Page 6: ...555 1265 595 459 40 100 1820 860 699 1670 790 611 1470 695 525 1255 590 443 50 125 1740 820 664 1600 755 575 1420 670 496 1215 575 414 60 150 1635 770 624 1530 720 544 1350 635 464 1175 555 400 70 17...

Page 7: ...t with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G40UH 48C 135 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Extern...

Page 8: ...filter not furnished field provided in place Also see Filter Air Resistance table G40UH 60C 110 1 2 3 with 3 4 hp motor PERFORMANCE Single Side Return Air Air volumes in bold require field fab ricated...

Page 9: ...le filter not furnished field provided in place Also see Filter Air Resistance table G40UH 60C 110 with 1 hp motor PERFORMANCE Single Side Return Air Air volumes in bold require field fabricated trans...

Page 10: ...able filter not furnished field provided in place Also see Filter Air Resistance table G40UH 60D 135 1 2 3 with 3 4 hp motor PERFORMANCE Single Side Return Air Air volumes in bold require field fab ri...

Page 11: ...5 791 1545 730 656 30 75 2235 1055 1234 2045 965 914 1820 860 774 1540 725 642 40 100 2160 1020 1240 1985 935 886 1800 850 755 1540 725 628 50 125 2065 975 1170 1925 910 863 1745 825 726 1535 725 614...

Page 12: ...s Watts 00 0 2670 1260 1386 2325 1095 1048 1970 930 857 1700 800 706 10 25 2580 1215 1342 2320 1095 1045 1965 925 842 1690 795 696 20 50 2510 1185 1311 2255 1065 985 1960 925 817 1640 775 662 30 75 24...

Page 13: ...pressure regulator setting Manifold Pressure Outlet in w g kPa FUEL ALTITUDE ft m FUEL 0 10 000 0 3048 Natural Gas 3 5 87 LPG Propane 10 0 2 49 HIGH ALTITUDE G40UH 1 1 High Altitude Orifice Kit Natur...

Page 14: ...Orifices Ignitor Bracket Burner Bottom Shield Limit Shield Secondary Limit as required NOx Units Only G40UH X PARTS ARRANGEMENT FIGURE 1 Gas Manifold 135 and 155 kBtuh units only Flame rollout switch...

Page 15: ...GURE 3 G40UH X HEATING COMPONENTS COMBUSTION AIR INDUCER PROVE SWITCH PRIMARY LIMIT PRIMARY LIMIT SHIELD GAS VALVE ROLLOUT SWITCHES MANIFOLD BURNER ASSEMBLY NOx Insert NOx Units Only HEAT EXCHANGER FL...

Page 16: ...NG Shock hazard Disconnect power before servicing Control is not field repairable If control is inoperable sim ply replace entire control Can cause injury or death Unsafe operation will result if repa...

Page 17: ...f 35 seconds After a total of five trials for ignition including the initial trial the control goes into Watchguard Flame Failure mode After a 60 min ute reset period the control will begin the igniti...

Page 18: ...OFF Circuit board failure or control wired incorrectly OFF ON y FAST FLASH SLOW FLASH Main power polarity reversed Switch line and neutral SLOW FLASH FAST FLASH Low flame signal See Table 15 for flam...

Page 19: ...nal designations See table 4 for troubleshooting diagnostic codes The mini nitride ignitor is made from a non porous high strength proprietary ce ramic material that provides long life and trouble fre...

Page 20: ...ote the supply air temperature at the instant the blower is de energized Adjust the fan off delay to achieve a supply air temperature between 90 110 at the instant the blower is de ener gized Longer d...

Page 21: ...ion air inducer may be rotated clockwise or counterclockwise by 90 to allow for vertical vent discharge in a horizontal application Remove the four mounting screws rotate the assembly assembly consist...

Page 22: ...HP motors have 2 flat sides and are matched with blower wheels with 2 set screws 10 Primary Limit Control S10 The primary limit S10 on G40UH X units is located in the heating vestibule panel When exc...

Page 23: ...3 Combustion Air Inducer Proving Switch S18 G40UH X series units are equipped with a combustion air proving switch located on the combustion air inducer orifice bracket The switch is connected to the...

Page 24: ...utes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruc tions If you do not smell gas go to next step 8 Honeyw...

Page 25: ...ck gas line pressure with unit firing at maximum rate Low pres sure may result in erratic operation or underfire High pres sure can result in permanent damage to gas valve or over fire See table 12 fo...

Page 26: ...ate reading shut off all other gas appliances connected to meter IMPORTANT For safety shut unit off and remove manometer as soon as an accurate reading has been obtained Take care to replace pressure...

Page 27: ...S A Blower Operation and Adjustment NOTE The following is a generalized procedure and does not apply to all thermostat controls 1 Blower operation is dependent on thermostat control system 2 Generally...

Page 28: ...ning furnace Cleaning the heat exchanger requires a steel spring snake a reversible drill and a vacuum cleaner The steel spring snake may be constructed by purchasing a 4 ft long by 1 4 diameter steel...

Page 29: ...section DO NOT BEND 15 Replace burner manifold assembly onto vestibule panel 16 Reconnect wires to pressure switch roll out switch gas valve and combustion air inducer Refer to unit wiring diagram 17...

Page 30: ...or control goes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control A92 energizes ignitor A 20 sec ond warm up period begins 5 Gas valve op...

Page 31: ...SECOND GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLA...

Page 32: ...GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Seque...

Page 33: ...LOWER OFF HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WAT...

Page 34: ...D SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY COOLING SPEED EAC H TERM ENERGIZED COMPRESSO...

Page 35: ...S ENERGIZED THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL H SPEED EAC H TERM REMAINS ON THERMOSTAT OPENS CONTROL G ENERGIZES SYSTEM FAN AT HEAT...

Page 36: ...nto 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 Ignition control A92 energizes ignitor A 20 second warm up period begins 5 Gas valve opens for a 4 second...

Page 37: ...INIMUM OF 1 SECOND GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED...

Page 38: ...DE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILURE CODE IS 60 MINUTE RESET PERIOD COMPLETE YES 4 SECONDS YES HAS CONTROL RESET IGNITION SEQUENCE FO...

Page 39: ...ROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS SYSTEM FAN AND EA...

Page 40: ...ED THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G EN...

Page 41: ...the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace code LED 1 O 1 2 2 Roll out switch failure ACTION 1 Check continuity across roll out switch Replace...

Page 42: ...IT FAILS TO FIRE IN THE HEATING MODE COMBUSTION AIR BLOWER DOES NOT ENERGIZE Condition Possible Cause Corrective Action Comments 2 1 Unit operates with a cooling or contin uous fan demand Combustion a...

Page 43: ...a heating demand Diagnostic lights flash the pressure switch failure code 2 5 minutes after heating demand 3 1 2 Prove switch does not close due to obstructions in the pressure lines ACTION 1 Remove...

Page 44: ...e switch code LED 1 Off LED 2 Slow Flash 5 1 1 Low pressure differential at the prove switch ACTION 1 Check for restricted exhaust vent Remove all blockage ACTION 2 Check for proper vent sizing See in...

Page 45: ...exchanger openings Cor rect the location of the burners if necessary 5 4 Combustion air inducer energizes with a heating demand B li ht hl d th it 5 4 1 Poor Venting ACTION 1 Check vent pipe and remo...

Page 46: ...tion Comments 7 0 Indoor blower fails to operate in continuous fan cooling or heating mode 7 1 1 Miswiring of furnace or improper con nections at control or indoor blower motor ACTION 1 Correct wiring...

Reviews: