BLOWER DATA
G40UH−36C−110 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1555
735
715
1335
630
575
1085
510
460
925
435
365
0.05
12
1540
725
705
1330
630
555
1080
510
450
920
435
360
0.10
25
1525
720
690
1320
625
545
1075
505
440
915
430
355
0.15
37
1510
715
680
1310
620
535
1070
505
430
910
430
350
0.20
50
1490
705
670
1295
610
525
1065
505
420
900
425
340
0.25
62
1465
690
655
1280
605
510
1060
500
415
890
420
335
0.30
75
1440
680
645
1260
595
495
1050
495
405
880
415
330
0.40
100
1385
655
615
1230
580
485
1030
485
390
865
410
320
0.50
125
1320
625
590
1190
560
460
995
470
375
835
395
300
0.60
150
1260
595
570
1135
535
430
960
455
355
815
385
295
0.70
175
1190
560
545
1075
505
410
915
430
345
775
365
285
0.80
200
1090
515
515
970
460
385
860
405
325
760
360
280
0.90
225
975
460
485
880
415
360
790
375
305
705
335
275
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G40UH−48B−070 PERFORMANCE
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
2080
980
846
1810
855
764
1535
725
634
1295
610
519
.10
25
2030
955
810
1790
845
714
1520
715
600
1285
605
492
.20
50
1955
920
767
1760
830
675
1515
715
566
1275
600
477
.30
75
1885
890
732
1710
805
640
1505
710
555
1265
595
459
.40
100
1820
860
699
1670
790
611
1470
695
525
1255
590
443
.50
125
1740
820
664
1600
755
575
1420
670
496
1215
575
414
.60
150
1635
770
624
1530
720
544
1350
635
464
1175
555
400
.70
175
1545
730
597
1420
670
501
1270
600
432
1080
510
368
.80
200
1400
660
554
1295
610
462
1135
535
392
990
465
343
.90
225
1250
590
512
1125
530
419
1050
495
372
875
410
310
NOTES − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G40UH−48B−090 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1970
930
790
1810
855
735
1585
750
670
1340
630
565
0.05
12
1940
915
780
1785
840
715
1580
745
650
1335
630
555
0.10
25
1915
905
765
1760
830
695
1570
740
630
1325
625
540
0.15
37
1880
885
745
1730
815
660
1560
735
615
1325
625
530
0.20
50
1840
870
730
1700
800
620
1545
730
600
1320
625
520
0.25
62
1805
850
715
1670
790
625
1520
715
585
1310
620
510
0.30
75
1765
835
695
1640
775
625
1490
705
565
1295
610
500
0.40
100
1695
800
670
1570
740
595
1440
680
540
1260
595
480
0.50
125
1600
755
635
1490
705
560
1360
640
505
1195
565
450
0.60
150
1505
710
600
1400
660
530
1285
605
480
1140
540
425
0.70
175
1395
660
565
1265
595
485
1170
550
440
990
465
380
0.80
200
1250
590
520
1100
520
445
975
460
390
905
425
355
0.90
225
1005
475
460
870
410
385
900
425
365
810
380
325
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.