Ju
ne
20
18
474 Legrand PDU User Guide
abo ve upper critical
Upper Critical
abo ve upper warning
Upper Warning
normal
Lower Warning
belo w lower warning
Lower Critical
belo w lower critical
Available sensor states:
The more thresholds are enabled for a sensor, the more sensor states are available for it. The "normal' state
is always available regardless of whether any threshold is enabled.
For example:
When a sensor only has the Upper Critical threshold enabled, it has two sensor states: normal and
above upper critical.
When a sensor has both the Upper Critical and Upper Warning thresholds enabled, it has three sensor
states: normal, above upper warning, and above upper critical.
States of "above upper warning" and "below lower warning" are warning states to call for your attention.