Outlet Configuration Commands
An outlet configuration command begins with
outlet
. Such a command allows you to configure an individual
outlet.
Changing the Outlet Name
This command names an outlet.
config:#
outlet <n> name "<name>"
Variables:
<n> is the number of the outlet that you want to configure.
<name> is a string comprising up to 64 ASCII printable characters. The <name> variable must be
enclosed in quotes when it contains spaces.
Changing an Outlet's Default State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of an outlet after the Legrand PDU powers up.
config:#
outlet <n> stateOnDeviceStartup <option>
Variables:
<n> is the number of the outlet that you want to configure.
<option> is one of the options:
off
,
on,
lastKnownState
and
pduDefined.
Option
Description
off
Turn off the outlet.
on
Turn on the outlet.
lastKnownState Restore the outlet to the state prior to last PDU
power down.
pduDefined PDU-defined
setting.
Note: Setting the outlet's default state to an option other than
pduDefined
overrides the PDU-defined default
state on that outlet. See
Setting the PDU-Defined Default Outlet State