Ju
ne
20
18
156 Legrand PDU User Guide
Examples:
To access Slave 1 via HTTPS, the IP address is:
https://192.168.84.77:50001/
To access Slave 1 via HTTP, the IP address is:
http://192.168.84.77:50101/
To access Slave 1 via SSH, the command is:
ssh -p 50201 192.168.84.77
Slave 2 device:
Position code for Slave 2 is '02' so each port number is 5NN02 as shown below.
Protocols
Port numbers
HTTPS 50002
HTTP 50102
SSH 50202
TELNET 50302
SNMP 50502
MODBUS 50602
Examples:
To access Slave 2 via HTTPS, the IP address is:
https://192.168.84.77:50002/
To access Slave 2 via HTTP, the IP address is:
http://192.168.84.77:50102/
To access Slave 2 via SSH, the command is:
ssh -p 50202 192.168.84.77
Adding, Removing or Swapping Cascaded Devices
Change a device's cascading mode first before adding that device to a cascading chain, or before
disconnecting that device from the chain.
If you only want to change the cascading mode of an existing chain, or swap the master and slave device,
always start from the slave device.
Note: If the following procedures are not followed, a networking issue occurs. When a networking issue
occurs, check the cascading connection and/or software settings of all devices in the chain. See
Cascading
Troubleshooting
(on page 482).
To add a device to an existing chain:
1. Connect the device you will cascade to the LAN and find its IP address, or connect it to a computer.
2. Log in to this device and set its cascading mode to be the same as the existing chain's cascading mode.
See
Setting the Cascading Mode
(on page 150).
3. (Optional) If this device will function as a slave device, disconnect it from the LAN after configuring the
cascading mode.
4. Connect this device to the chain, using either a USB or Ethernet cable.
To remove a device from the chain:
1. Log in to the desired cascaded device, and change its cascading mode to None.
Exception: If you are going to connect the removed device to another cascading chain, set its cascading
mode to be the same as the mode of another chain.