Legrand PDU User Guide 221
To modify settings, make necessary changes and then click Save.
To delete it, click
, and then confirm it on the confirmation message.
Monitoring Server Accessibility
You can monitor whether specific IT devices are alive by having the Legrand PDU continuously ping them.
An IT device's successful response to the ping commands indicates that the IT device is still alive and can be
remotely accessed.
This function is especially useful when you are not located in an area with Internet connectivity.
Legrand PDU can monitor the accessibility of any IT device, such as database servers, remote
authentication servers, power distribution units (PDUs), and so on. It supports monitoring a maximum of 8
devices.
The default ping settings may not be suitable for monitoring devices that require high connection reliability so
it is strongly recommended that you should adjust the ping settings for optimal results.
Tip: To make the Legrand PDU automatically log, send notifications or perform other actions for any server
monitoring events, you can create event rules. See
Event Rules and Actions
(on page 184). An example is
available in
Example: Ping Monitoring and SNMP Notifications
(on page 222).
To add IT equipment for ping monitoring:
1. Choose Device Settings > Server Reachability.
2. Click
.
3. By default, the "Enable ping monitoring for this server" checkbox is selected. If not, select it to enable this
feature.
4. Configure the following.
Field
Description
IP address/hostname IP address or host name of the IT
equipment which you want to monitor.
Number of successful
pings to enable
feature
The number of successful pings required to
declare that the monitored equipment is
"Reachable." Valid range is 0 to 200.
Wait time after
successful ping
The wait time before sending the next ping
if the previous ping was successfully
responded. Valid range is 5 to 600
(seconds).
Wait time after
unsuccessful ping
The wait time before sending the next ping
if the previous ping was not responded.
Valid range is 3 to 600 (seconds).
Number of
consecutive
unsuccessful pings
for failure
The number of consecutive pings without
any response before the monitored
equipment is declared "Unreachable."
Valid range is 1 to 100.
Wait time before
resuming pinging
after failure
The wait time before the Legrand PDU
resumes pinging after the monitored
equipment is declared "Unreachable."
Valid range is 1 to 1200 (seconds).