6: Configuration via Serial Mode or Telnet Port
WiPort Embedded Wireless Device Server User Guide
61
Table 5-14. Pack Control Options
Option
7 6 5 4 3 2 1 0
Packing Interval
Interval: 12ms
0 0
Interval: 52ms
0 1
Interval: 250ms
1 0
Interval: 5sec
1 1
Trailing Characters
None
0 0
One
0 1
Two
1 0
Send Characters
2-Byte Send Character
Sequence
1
Send Immediately After
Send chars
1
Packing Interval:
Packing Interval defines how long the unit should wait before
sending accumulated characters. This wait period is between successive network
segments containing data. For alternate packing, the default interval is 12 ms.
Trailing Characters:
In some applications, CRC, Checksum, or other trailing
characters follow the end-of-sequence character; this option helps to adapt frame
transmission to the frame boundary.
Send Characters:
If
2-Byte Send Character Sequence
is enabled, the unit interprets the
sendchars as a 2-byte sequence; if this option is not enabled, the unit
interprets them independently.
If
Send Immediately After Characters
is not set, any characters already in
the serial buffer are included in the transmission after a "transmit" condition is
found. If this option is set, the unit sends immediately after recognizing the
transmit condition (sendchar or timeout).
Note:
A transmission might occur if status information needs to be
exchanged or an acknowledgment needs to be sent.
DisConnTime (Inactivity Timeout)
Use this parameter to set an inactivity timeout. The unit drops the TCP connection to
port 10001/10002* if there is no activity on the serial line before the set time expires.
Enter time in the format
mm:ss
, where m is the number of minutes and s is the
number of seconds.
Note*:
The default port number for Port 1 is 10001 and 10002 for Port 2. However,
port numbers may be set to a different value.
DisConnTime (0: 0) ?: