ALM (Alarm) LED
The
ALM
(Alarm) LED lights if monitored temperature or internal voltages are
exceeded.
Issue critical stage for High / Low Voltage alarm (Power A or B Voltage)
Lit Alarm LED in RED Color if Test-point (max) < Volts or if Test-point (min) < Volts.
V1 (PHY, TTL, LED, SFP): (max: 3.465V, min: 3.135V) (+- 5%)
V2 (MAC): (max: 2.625V, min: 2.375V) (+- 5%)
V3 (MAC, DDR): (max: 1.575V, min: 1.425V) (+- 5%)
V4 (MAC): (max: 1.05V, min: 0.95V) (+- 5%)
Issue critical stage for High Temperature alarm: Lit Alarm LED in RED Color if Test-point (max) < temperature
max: 100'C.
You can view temperature and voltage settings at Monitor > Port > SFP Detail Info.
You can view and configure current trap event severity parameters via the Web Interface at Configuration >
System > Alarm Notification > Trap Event Severity. See the
Web User Guide
for more information.