Industrial Power Supply 25104
Note
:
Both the switch and Power Supply 25104 must have their ground terminals
connected to earth ground.
Output
Output Voltage
48VDC
Current Rating
5A
Power Rating
240 Watts
Ripple & Noise Max
120mVp-p
Voltage Range
48~55VDC
Voltage Tolerance
±1.0%
Line Regulation
±0.5%
Load Regulation
±1.0%
Setup, Rise Time
300ms, 60ms
Hold Up Time
20ms
Input
Voltage Range
Switch Selectable. 88~132VAC. 124~370VDC
Frequency Range
47~63Hz
Efficiency
94%
AC Current (Typical) 2.6A@115VAC. 1.3A@230VAC
Inrush Current (Cold) 33A@115VAC. 65A@230VAC
Protection
Overload 105~160%. Overvoltage 56~65V.
Environment
Operating Temp. -25ºC~+70ºC. Storage Temp. -40ºC~+85ºC.
Operating Humidity
20~95% non-condensing
Features
94% High Efficiency. 150% Peak Load. Protected against: Short Circuit, Overload, Over
Voltage, Overheating. Convection air cooling. DIN rail mountable (S35/7.5 or TS35/15).
RoHS compliant. MTBF 169.3 Khrs. Dimensions (mm): 63W, 125.2H, 113.5D. Weight
1.03Kg.
Standards
Safety: UL508, TUV EN62368. Vibration: IEC60068-2-6. EMC Emission: EN55022, CISPR22
Class B, EN61000-3-2, |EN61000-3-3. EMC Immunity: EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11, EN55024,
EN61000-6-2, EN50082-2, EN61204-3, SEMI F47, GL Approved.
Mean Well SDR-240-48.
INPUT
: 100-240VAC 2.6A 50/60 Hz.
OUTPUT
: 48V - 5A. “Use copper wire only”.
“Maximum surrounding air temperature: 60°C”. “Instructions for installation in a pollution degree 2
environment”.