background image

4

INSTALLATION

Unpack the Dispenser

1. 

Set shipping carton upright on the floor then cut package 

banding straps and remove.

2.  Open top of carton and remove interior packaging. 
3. 

Lift carton up and off of the unit.

4.  Remove plywood shipping base from unit by moving unit so 

that one side is off the counter top or table allowing access 

to screws on the bottom of the plywood shipping base.

 

If unit is to be transported, it is advisable to leave the 

unit secured to the plywood shipping base.

 

NOTE

Inspect unit for concealed damage. If evident, notify 

delivering carrier and file a claim against the same.

NOTE

5.  Remove accessory kit and loose parts from ice compartment.
6.  Clean ice chute and ice bin using cleaning instruction on  

page 20. 

Selecting/Preparing Counter Location

1.  Select a level, well ventilated location that is in close 

proximity to a properly grounded electrical outlet, within five 

(5) feet (1.5 m) of a drain, a water supply that meets the 

requirements shown in the Specifications section found on 

page 3, and away from direct sunlight or overhead lighting. 

2. 

Sufficient clearance must be provided, if an ice maker is not 

installed, to allow filling ice compartment from a five gallon 

bucket (a minimum of 16 inches is recommended). 

3.  The selected location should be able to support the weight of 

the dispenser, ice and possibly an icemaker being installed 

after counter cut out is made. Total weight (with icemaker) for 

this unit could exceed 800 pounds (363.6kg).

Lancer does 

NOT

 recommend the use of shaved or 

flake ice in the dispenser.

NOTE

4.  Unit may be installed directly on counter-top. Once installed 

directly on the counter, unit must be sealed to the count-

er-top with an FDA approved sealant.

5.  Select a location for the remote pump deck, syrup pumps, 

CO

2

 tank, syrup containers, and water filter (recommended).                                                                                  

6.  Cut out required opening for the water, syrup, and CO

2

 lines 

in the designated dispenser location.

In order to facilitate proper dispenser drainage, ensure 

that the dispenser is level, front to back and side to 

side. Place a level on the top of the rear edge of the 

dispenser. The bubble must settle between the level 

lines. Repeat this procedure for the remaining three 

sides. Level unit if necessary. For optimum perfor-

mance place the unit at a 0° tilt. The maximum tilt is 5°.

Leveling the Dispenser:

 

NSF listed units must be sealed to the counter.

NOTE

To ensure that beverage service is accessible to all 

customers, Lancer recommends that counter height 

and equipment selection be planned carefully. The 

2010 ADA Standards for Accessible Design states that 

the maximum reach height from the floor should be no 

more than 48” if touch point is less than 10” from the 

front of the counter, or a maximum of 46” if the touch 

point is more than 10” and less than 27” from the front 

of the counter. For more information about the  

customer’s legal requirements for the accessibility of 

installed equipment, refer to 2010 ADA Standards for 

Accessible Design - http://www.ada.gov.

NOTE

 

Si l’appareil doit être transporté, il est conseillé de le lais-

ser fixé sur la base d’expédition en contreplaqué.

REMARQUE

 

Inspectez l’appareil pour déceler des dommages cachés. 

Si l’appareil est endommagé, avisez le transporteur et 

soumettez-lui une réclamation.

REMARQUE

Lancer recommande de ne 

PAS

 utiliser de glace pilée ou 

de glace en écailles avec le distributeur.

NOTE

 

Toute unité homologuée NSF doit être scellée sur le 

comptoir.

NOTE

 

Afin de faciliter une vidange complète, assurez-vous que 

l’appareil est de niveau sur les axes avant arrière et gauche 

droit. Placez un niveau sur le bord arrière de la distribu-

trice. La bulle doit se situer entre les deux lignes. Répétez 

la procédure sur les trois autres côtés. Ajustez le niveau de 

l’appareil si nécessaire. Pour un résultat maximal, réglez 

l’inclinaison à 0°. L’inclinaison maximale est de 5°.

Mise à niveau de la distributrice

Pour s’assurer que le service de boissons est acces-

sible à tous les clients, Lancer recommande que la 

hauteur du comptoir et le choix de l’équipement soient 

soigneusement planifiés. Les normes ADA 2010 pour 

la conception accessible stipulent que la hauteur de 

portée maximale depuis le sol ne doit pas dépasser 48 

pouces si le point de contact est à moins de 10 pouces 

de l’avant du comptoir, ou un maximum de 46 pouces 

si le point de contact est plus à 10 ”et à moins de 27” 

de l’avant du comptoir. Pour plus d’informations sur les 

exigences légales du client concernant l’accessibilité 

des équipements installés, reportez-vous aux normes 

ADA 2010 pour la conception accessible - 

http://www.ada.gov.

REMARQUE

Summary of Contents for Twin Pour 30

Page 1: ...not be used by children or infirm persons without supervision This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or la...

Page 2: ...hez pas cet appareil dans une prise lectrique multiple partag e par d autres appareils Ne placez pas plusieurs prises d alimentation multiples portables ou alimentations lectriques portables l arri re...

Page 3: ...an air gap a backflow prevention device or another approved method to comply with NSF standards A leaking inlet water check valve will allow carbonated water to flow back through the pump when it is s...

Page 4: ...aining three sides Level unit if necessary For optimum perfor mance place the unit at a 0 tilt The maximum tilt is 5 Leveling the Dispenser NSF listed units must be sealed to the counter NOTE To ensur...

Page 5: ...at se trouve dans le bac gla ons Durant le cycle d agitation automatique et lors de la distribution des gla ons veiller ce que l espace soit suffisant entre le dessus de l amas de gla ons et le bas de...

Page 6: ...nect tubing to all syrup inlets See Plumbing Diagrams on page 26 for reference NOTE 12 Route drain hose from designated open type drain to fitting on Drip Tray and connect hose to fitting if applicabl...

Page 7: ...E 13 Attach fan bracket to fan assembly using screws provided Condensation Fan Installation 14 Install condensation fan on the underside of the unit by 1 pushing fan bracket into slots in the right wa...

Page 8: ...OT TURN ON CO2 SUPPLY AT THIS TIME WARNING 7 Repeat Step 6 for both low pressure CO2 regulators on the regulator manifold routed to the unit and the syrup pumps 5 Connect tubing routed from the tee at...

Page 9: ...the service menu for drink setup must be accessed 10 Access the Service Menu by turning the keyswitch clock wise to the third position 6 Turn on the power to the dispenser by pressing the on off toggl...

Page 10: ...oth of the low pressure regulators on the regulator manifold to 75 psi 0 517 MPa then tighten locknut with wrench 22 Activate each soda module until gas out 23 Plug in the remote carbonator pump deck...

Page 11: ...button on the lower left corner to return to the Valve Configuration Screen 7 Repeat Steps 3 and 5 for any of the other brand or flavor modules 8 Tap the Back button to return to the Service menu 12 T...

Page 12: ...bration button 2 Tap the Calibrate on the Water Valve to be calibrated Calibrating Plain Carbonated Water Modules Fill to 200 ml Graduated Cylinder CALIBRATION MAINTENANCE 4 Set the Timer to the ON po...

Page 13: ...r reference The water flow rate was set to 73 93 ml sec which makes the final syrup flow rate 14 79 ml s The finished drink flow rate dispensed will be 88 72 ml s NOTE A B C D Increase Decrease A Flow...

Page 14: ...ttach outer nozzle by pushing up and twisting clockwise until snug 5 Enter the brand calibration screen from the previous section steps 1 2 6 Set the Timer to the ON position and select Time as the Op...

Page 15: ...The following is a set of instructions on how to set up this feature If no sold out sensor is assigned then the Auto feature acts the same as the Ready feature NOTE Sold Out Features 1 From the Servic...

Page 16: ...d scroll down and press Accept to confirm and save changes It may take up to 10 minutes for a network connection to be established NOTE 2 From the service menu select Network Status to change connecti...

Page 17: ...into open port on the side of the PCB controller box 4 Access the Service menu on the left side screen and tap the Data Management button Update Brands Flavors 1 Create a USB drive with the updated b...

Page 18: ...ment aux lignes directrices de la NSF L exploitant de l quipement doit en assurer l entretien continu comme indiqu dans ce manuel ou selon les lignes directrices du minist re de la Sant afin d assure...

Page 19: ...n Box on page 21 Pull out unit if applicable and clean behind and underneath Check for any loose components or noises Other Supplies Needed 1 Clean cloth towels 2 Bucket 3 Extra nozzle 4 Sanitary glov...

Page 20: ...in the sanitizing solution using the nozzle brush dip the brush in the nozzle sanitizing solution and thoroughly brush the bottom of the inner nozzle body 6 Rinse the brush in warm 90 110 F 32 2 43 3...

Page 21: ...all sides of the Ice Bin and surface of the aluminum casting 5 Place syrup lines with BIB connectors and any adapters into cleaning solution 6 Activate each valve until lines are filled with cleaning...

Page 22: ...coming CO2 pressure is between 70 psi 0 483 MPa and 80 psi 0 552 MPa 2 Open shutoff fully 3 Remove soda flow control from valve and clean out any foreign material to ensure smooth spool movement Insuf...

Page 23: ...to syrup pump too low 5 Stalled or inoperative BIB pump 6 Kinked line 7 CO2 regulator malfunction 1 Replace syrup BIB as required 2 Open shutoff completely 3 Remove valve from mounting block open shu...

Page 24: ...Wiring harness not plugged in 3 PC board defective 4 Malfunctioning power supply 1 Connect dispenser to power source 2 Plug in wiring harness 3 Replace PC board 4 Check voltage to power supply Check f...

Page 25: ...ck BIB connector if still leaking then re place line 2 Replace o ring 3 Replace defective pump BIB pump fails to restart after bag replacement 1 BIB connector not on tightly 2 BIB connector is stopped...

Page 26: ...12 14 16 2 4 6 16 8 10 12 14 1 3 5 7 9 NC 11 13 15 NC 1 3 5 15 7 9 11 13 BLK WHT GRY BLK PUR BLU GRN YEL ORG RED BRN VIO BLK BLK GRN BLK BRN BLK ORG BLK BLK BLK GRY PUR BLU GRN YEL ORG RED BRN WHT BLK...

Page 27: ...R USB DC BLOCK OK POWER CORD CONDENSATION FAN PRIMARY PCB SECONDARY PCB POUR BUTTON POUR BUTTON GPIO ICE DOOR TRIGGER VALVEHARN RIGHT VALVEHARN LEFT SBC USB A TO USB B DIO PCB POWER SUPPLY USB A MALE...

Page 28: ...SATION FAN PRIMARY PCB SECONDARY PCB GRN DC FAN AC OUT AC VOLT TO SUPPLY GRN BLU BLK DIO PCB BLK RED RED BLK BLK RED DENOTES DEFAULT 3 2 SW2 SWITCH 2 POSITION DOES NOT MATTER 4 ON LANCER PN 06 3289 01...

Page 29: ...29...

Page 30: ...A HOSHIZAKI COMPANY 6655 Lancer Boulevard San Antonio TX 78219 lancerworldwide com...

Reviews: