LAARS Heating Systems
Page 2
model nomenclature
1 2
3
4 5 6 7 8
9
10
11
12
13
M G
1
SERIES
m G
USAGE
H -
HYDRONIC
V -
VOLUME
WATER
SIZE
MBTU/h
2 0 0 0
3 0 0 0
4 0 0 0
FUEL
n -
NATURAL
P -
PROPANE
COUNTRY
CODE
X -
USA/
CANADA
e -
EXPORT
*
OPTIONS CODE
X -
STANDARD
J
- CSD-1
ELEC SYSTEM
a - 110V, 1Ø
B - 220V, 1Ø
C - 208V, 3Ø
D - 480V, 3Ø
e - 600V, 3Ø
REVISION
1 -fIrSt
ASME
X -
“H” STAMP (MGH)
W -
“HLW” STAMP (MGV)
1.4 Warranty
LAARS Heating Systems’ MagnaTherm boilers are
covered by a limited warranty. The owner should
complete the warranty registration at
http://www.Laars.com
ALL wARRAnTy cLAiMS must be made by an
authorized LAARS Heating Systems representative.
claims must include the serial number and model
(this information can be found on the rating plate).
All claims must also include the installation date and
name of the installer. Shipping costs are not included
in the warranty coverage.
WarnInG
Electrical Shock Hazard
Electrical shock can cause severe injury, death or
property damage. Disconnect the power supply
before beginning installation or changing the
wiring to prevent electrical shock or damage to the
equipment. It may be necessary to turn off more
than one power supply disconnect.
All electrical wiring is to be done in accordance
with local codes, or in the absence of local codes,
with: 1) The National Electrical Code ANSI/NFPA
No. 70 - latest Edition, or 2) CSA STD. C22.1
“Canadian Electrical Code - Part 1.” This appliance
must be electrically grounded in accordance with
these codes.
1.3
Model Identification
consult the rating plate on the unit. The following
information describes the model number structure.
(1-2)
model Series Designation
M G = MagnaTherm
(3)
Usage
H = Hydronic
V = Volume Water
(4-7)
Size
2 0 0 0 = 1,999,000 BTU/hr input
3 0 0 0 = 3,000,000 BTU/hr input
4 0 0 0 = 4,000,000 BTU/hr input
(8)
fuel
N = Natural Gas
P = LP Gas
(9)
Country Code
X = USA / CANADA
E - Export (CE - non CSA)
(10)
option Code
X = Standard Unit
J = CSD1 Version
(11)
electrical System
A - 110V, (Single Phase)
B - 220V, (Single Phase)
C - 208V, (Three Phase)
D - 480V, (Three Phase)
E - 600V, (Three Phase)
(12)
additional options
X - “H” STAMP (MGH)
W - “HLW” STAMP (MGV)
(13)
revision
1 = First
WarnInG
MagnaTherm units must be installed in accordance
with the procedures detailed in this manual, or the
LAARS Heating Systems warranty will be voided.
The installation must conform to the requirements
of the local jurisdiction having authority, and,
in the United States, to the latest edition of the
National Fuel Gas Code, ANSI Z223.1/NFPA54. In
Canada, the installation must conform to the latest
edition of CSA B149.1 Natural Gas and Propane
Gas Installation Code, and/or local codes. Where
required by the authority having jurisdiction, the
installation of MagnaTherm boilers must conform
to the Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1.
Any modifications to the boiler, its gas controls, or
wiring may void the warranty. If field conditions
require modifications, consult the factory
representative before initiating such modifications.
*
Not CSA approved
Altitude:
Gas input rating of the MagnaTherm shall be
used for elevations up to 2000 ft (600 m). The
input rating at elevations above 2000 ft (600
m) shall be reduced at a rate of 4 percent for
each 1000 ft (300 m) above sea level before
selecting the equipment size.