MagnaTherm Boilers and Water Heaters
Page 71
code Description
Lockout
or Hold
Procedure
26
internal fault:
Static flame ripple
H
internal fault
1. Reset module
2. if fault repeats, replace module.
27
internal fault:
Flame rod shorted to ground detected
H
internal fault
1. Reset module
2. if fault repeats, replace module.
28
internal fault:
A/D linearity test fails
H
internal fault
1. Reset module
2. if fault repeats, replace module.
29
internal fault:
Flame bias cannot be set in range
H
internal fault
1. Reset module
2. if fault repeats, replace module.
30
internal fault:
Flame bias shorted to adjacent pin
H
internal fault
1. Reset module
2. if fault repeats, replace module.
31
internal fault:
SLO electronics unknown error
H
internal fault
1. Reset module
2. if fault repeats, replace module.
32-46 internal fault:
Safety Key 0 through 14
L
internal fault
1. Reset module
2. if fault repeats, replace module.
47
Flame Rod to ground leakage
H
internal fault
1. Reset module
2. if fault repeats, replace module.
48
Static flame (not flickering)
H
internal fault
1. Reset module
2. if fault repeats, replace module.
49
24 VAc voltage low/high
H
1. check the module and display connections.
2. check the module power supply and make
sure that frequency, voltage and VA meet the
specifications.
50
Modulation fault
H
internal sub-system fault.
1. Review alert messages for possible trends.
2. correct possible problems.
51
Pump fault
H
internal sub-system fault.
1. Review alert messages for possible trends.
2. correct possible problems.
52
Motor tachometer fault
H
internal sub-system fault.
1. Review alert messages for possible trends.
2. correct possible problems.