LAARS Heating Systems
Page 80
code Description
Lockout
or Hold
Procedure
200
invalid lightoff rate setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
201
invalid lightoff rate proving setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
202
invalid MFEP (Main Flame Establishing
Period) time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
203
invalid MFEP (Main Flame Establishing
Period) flame failure response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
204
invalid nTc sensor type setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
205
invalid Outlet high limit response
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
207
invalid Pii (Pre-ignition interlock)
enable setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
210
invalid Postpurge time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
211
invalid Power up with lockout setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
212
invalid Preignition time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
213
invalid Prepurge rate setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.