MagnaTherm Boilers and Water Heaters
Page 15
3.4
Common Vent test
note -
This section does not describe a method
for common venting MagnaTherm’s. It describes
what must be done when a unit is removed from
a common vent system. MagnaTherm’s require
special vent systems and fans for common vent.
Contact the factory if you have questions about
common venting MagnaTherm’s.
when an existing boiler is removed from a common
venting system, the common venting system is likely
to be too large for proper venting of the appliances
remaining connected to it.
At the time of removal of an existing boiler,
the following steps shall be followed with each
appliance remaining connected to the common
venting system placed in operation, while the other
appliances remaining connected to the common
venting system are not in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion or
other deficiencies which could cause an unsafe
condition.
3. insofar as is practical, close all building doors
and windows and all doors between the space
in which the appliances remaining connected
to the common venting system are located
and other spaces of the building. Turn on any
clothes dryers and any appliance not connected
to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom
exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
4. Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after five minutes of main burner operation. Use
the flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return the doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the national Fuel Gas code,
AnSi Z223.1/nFPA 54 and/or cAn/cSA
B149.1, national Gas and Propane installation
code. when resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum
size as determined using the appropriate tables
in Appendix F in the national Fuel Gas code,
AnSi Z223.1 nFPA 54 and/or cAn/cSA
B149.1, national Gas and Propane installation
code.
Au moment du retrait d’une chaudiére existante, les
mesures suivantes doivent être prises pour chaque
appareil toujurs raccordé au systéme d’évacuation
commun et qui fonctionne alors que d’autres
appareils toujours raccordés au système d’évacuation
ne fonctionnent pas:
1. Sceller toutes les ouvertures non utilisées du
système d’évacuation.
2. inspecter de facon visuelle le système
d’évacuation pour déterminer la grosseur
et l’inclinaison horizontale qui conviennent
et s’assurer que le système est exempt
d’obstruction, d’étranglement, de fuite, de
corrosion et autres défaillances qui pourraient
présenter des risques.
3. Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l’espace où les appareils toujours
raccordés au système d’évacuation sont installés
et les autres espaces du bâtiment. Mettre en
march les sécheuses, tous les appareils non
raccordés au système d’évacuation commun
et tous les ventilateurs d’extraction comme
les hottes de cuisinière et les ventilateurs des
salles de bain. S’assurer que ces ventilateurs
fonctionnent à la vitesse maximale. ne pas faire
fonctionner les ventilateurs d’été. Fermer les
registres des cheminées.
4. Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat
de facon que l’appareil fonctionne de facon
continue.
5. Faire fonctionner le brûleur principal pendant 5
min ensuite, déterminer si le coup-tirage déborde
à l’ouverture de décharge. Utiliser la flamme
d’une allumette ou d’ une chandelle ou la fumée
d’ une cigarette, d’un cigare ou d’une pipe.
6. Une fois qu’il a été détermineé, selon la méthode
indiquée ci-dessus, que chaque appareil
raccordé au système d’évacuation est mis à l’air
libre de facon adéquate. Remettre les portes