This document is the exclusive property of FTFM La Toulousaine and must on no account be copied. It may be modified at any time in accordance with product changes.
_N°7386
Installation_Totem operator (Sliding gate)
09/21
p.22
Malfunction
Possible cause
Solution
The gate does not reverse its
movement on contact with the object
-
The gate is poorly adjusted
-
Resume gate setting and perform self
-
learning
Operator unlocks, the gate opens
and closes with difficulty by hand
-
Faulty emergency release
-
Gate locks up
-
Repair the emergency release
-
Check the gate (guiding rail, rollers, etc.)
The gate won't start
-
Disengaged operator
-
The cells are on standby
-
Safety LED is on
-
Disengage the operator.
-
Close the gate and issue a run command
-
Check the connection of the management
board and the alignment of the cells
Cells (if existing)
-
Open/Close the gate over the
sensors, safety LED does not light
(depending on DIP setting 4)
-
Cable breakage, loose terminals
-
Congested cells
-
Deregulated cells
-
Defective cells
-
Check wiring, retighten terminals
-
Clean the cells
-
Align the cells
-
Replace cells
Automation fails to close the gate
-
The electric power source of the
cells is interrupted
-
Power failure
-
Power failure, when the gate was
in the intermediate position and
therefore switched to hold to run
mode
-
Check connection, replace fuse
-
-
Move the gate in hold to run mode until the
opening or closing run limit is reached and lock
it.
The automated system opens the gate
and then does not react to a command
from the transmitter
-
The safety input has been triggered
(example : defective sensors),
safety LED flashes
-
Eliminate the obstacle obstructing the cells
-
Repair the cells
-
The transmitter was programmed incorrectly
The opening or closing speed varies
-
The automated system starts and
slows down before reaching the
limit
-
switch
-
Normal behavior, the automated system starts
at maximum speed and then slows down before
reaching the other limit
-
switch
The gate can only be operated as long
as you keep the button of a transmitter
pressed
-
Hold to run mode activated
-
Deactivate hold to run mode, see chapter DIP
switch settings or correct the defective security
device
All LEDS flash
on the radio receiver
-
All 112 entries (maximum)
in memory are occupied
-
Remove transmitters that are no longer in use
-
Install an additional radio receiver
One of the LEDS on the radio receiver
stays on
-
The radio signal is received,
a button on the transmitter may
be defective or there is an external
signal
-
Remove the battery from the transmitter
-
Wait until the external signal stops emitting
One of the LEDS on the radio receiver
lights up
-
The radio receiver is in program-
ming mode and waits for a radio
code from the transmitter
-
Press the key on the transmitter
"Safety" LED flashing sequence
Meaning
Emergency unlocking, emergency stop
or stop button actuated
Safety contact strip twisted
or disconnected
Passing in front of the cells
Operating time > 90 seconds,
stroke too short or too long
System Error : The control unit has a fault
or the gate is overloaded
"Status" LED flashing sequence
Meaning
Sleep mode is activated
Gate open, time delay elapses before
automatic closing
Insufficient battery charge