19.0 SMS warning system
The PCT400 can, when it is connected to the internet, communicate the SMS server by KSM-Stoker in
Denmark.
And when it is connected to the SMS server, the client is able to receive all kind of boiler alarm, as SMS
text on his mobile phone.
List of available alarm text is written here below, with description.
Alarm No. SMS Text
Description
007
Startup timeout
High O2 to long time
008
Module problem
Overload switch or fuse blowen
009
Hopper cover open
Close it
☺
010
Boiler temp > max
Software alarm
011
Boiler have lost water
Water pressure gone
012
Boiler is overheated
High temp switch
014
Hydraulic timeout
Hydraulic have been running to long
016
Fuel storage nearly empty
Fuel needed
018
O2 sensor broken
New O2 probe needed
020
Transport timeout
Transport system have been running to long
022
023
Fluefan alarm
Check Fan and inverter
024
Transport SW
Service lid is open
026
Module comm alarm
Check module
027
Alarm hydraulic pump
Electrical motor at the hydraulic unit overheated
028
Flame damper SW
Check SW and
029
Hydraulic oil level
More oil needed
030
Hydraulic oil temp
Check oil pressure switch
031
Fan alarm
Check fan and inverter
032
HZ alarm fluefan
Flue fan or Inverter broker HZ < 5 for 15 sek
033
Vac. Alarm fluefan
Door open or dirty boiler Pa < 5 for 15 sek
034
Alarm bypass SW
Problems with bypass valve on bag filter
035
Ignition timeout
No flame in time
036
Alarm boiler temp. Low
To high demand or boiler dirty
037
Alarm Smoke temp. high
Boiler dirty or to high output