- 63 -
13.11 Automatic boiler cleaning.
Along with the development of the KSM-Multistoker XXL, it has become easier to maintenance your
boiler.
The boiler have as standard automatic heat exchanger cleaning system. But even though the boiler is
equipped with these automatic cleaning spiral, the heat exchanger pipe, must be cleaned manually
minimum once a year.
In all smoke pipes there are mounted spirals which have
two functions.
They clean the heat exchanger pipe when they rotate, and
because off those spiral the speed of the hot smoke gasses
will be slower, that reduce the loses into the chimney and
give the boiler a higher efficiency.
The spirals are driven by small clutches which are
mounted on the inside of the door
The motor that turn the spirals, are placed on the
outside of the door.
Bushing
Main bearing
All the small bushing, must be greased minimum
Twice a year, as well as the main bearing in the
Middle, behind the gearbox.