- 19 -
7.0 Software instructions
Menu structure.
The menu structure in the PCT400 is designed in the same way as we know it from example Windows.
The menu is divided in different, so it should be easy to go to the wanted function.
In the following chapters, all function and parameter will be carefully explained.
In parents after the menu line, we have put in the standard value.
7.1 Logs.
In the KSM boilers from 13 to 95kw it is possible to us logs, as supplement to the pellets or wood chip,
and for this the PCT400 have a special function.
We don’t use this function in a XXL boiler
7.2 Run.
Menu / Run
The run chapter contains all parameters which is significance for the different functions in run mode.
7.2.1 Boiler temp
Menu / Run / Boiler temp
In this chapter you can find all parameters concerned the boiler temperature while operating.
7.2.1.1 Set temperature °C
Menu / Run / Boiler temp / Set temp °C (75°C)
The working temperature of the boiler. To keep the corrosion warranty on the boiler, you are not allowed
to go below 70°C
7.2.1.2 Go pause temp +°C
Menu/ / Run / Boiler temp. / Go to pause +C (5°C)
It is the limit of how many degrees the temperature can go above the boilers set temperature before the
boiler are forced to go in pause mode.
If the value is to low, the controller don’t have the optimal to modulate the boiler output down, without
hitting the pause mode.
7.2.1.3 Back to run mode -°C
Menu / Run / Boiler temp / Back to run mode –C (1°C)
The value of how many degrees the temperature is have to go below SP before the boiler startup again.
7.2.1.4 Max output %
Menu / Run / Boiler temp / Max output % (100%)
The standard value is 100%, but if the installed boiler is too big, it can be a good idea to reduce the
maximum output.