- 26 -
7.6.1.1 Run as stoker screw.
Menu / Accessories / Transport auger / Run as stoker screw (no)
When using very dry or light fuel, it can be helpful to let the stoker screw runs all the time, to avoid back-
fire and let the transport auger runs as dispense auger (stoker screw).
Just select yes or no.
7.6.1.2 After run stoker screw %.
Menu / Accessories / Transport auger / After run stokerscrew % (150%)
When the transport auger is running as dispense auger, the stoker screw have to run longer, than the
transport auger, so the stoker screw is not overfilled. The after run setting are in %.
If the settings are 150%, the stoker screw will run 7,5sek if the transport auger run for 5sek.
7.6.1.3 After run before pause s.
Menu / Accessories / Transport auger / After run before pause s. (15 sek.)
Before the boiler switch into pause mode, it is important that the stoker screw runs empty. How long time
it have to run to be empty, is different from boiler to boiler.
7.6.1.4 Fuel delay.
Menu / Accessories / Transport auger / Fuel delay m. (1 min.)
The transport auger should not start and stop more than needed, because it load the gearbox and the
electric motor.
When the value is set to 1 min. the transport auger will not start, before 1 min after the fuel sensor
indicate that fuel is needed.
7.6.1.5 Stop delay s.
Menu / Accessories / Transport auger / Stop delay s. (2 sek.)
To make sure that the transport auger doesn’t stop, as soon the fuel sensor is activated by a piece of
woodchip.
That’s why it is possible to delay the transport screw from stopping.
7.6.1.6 Feeder timeout m.
Menu / Accessories / Transport auger / Feeder timeout m. (30 min.)
The function “Feeder timeout”, will stop the transport auger, if the augers have been running for more
than the indicated time.
This could have happened if the fuel stock is empty.
7.6.1.7 Delay start next s.
Menu / Accessories / Transport auger / Delay start next s. (0 sek.)
In some installations it can be helpful, to be able to control when the next transport auger will start.
Standard is right away (0).
If the fuel can block up between 2 augers, we can give a bit off time to remove the fuel, befor the next
transport auger start again.
7.6.1.8 Cell lock delay stop s.
Menu / Accessories / Transport auger / Cell lock delay stop s. (0 sek.)
If the boiler are installed with cell lock, and used for straw, it make sense to let the cell lock run extra by
each time.
The reason is to empty the cell lock total, so the is no risk that some straw will block the fuel sensor, and
make the controller believe there is enough fuel.